EasyManuals Logo

GE P642 User Manual

GE P642
592 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #139 background imageLoading...
Page #139 background image
Ibias /Inom
I
diff/Inom
Is1
Is-CTS
I
s-HS1
Is-HS2
Is2
K
1
K2
Restraint region
O
perate region
V03127
TC and CT errors
Figure 44: Effect of CTS restrain
3.8.8 CIRCUITRY FAIL ALARM
Under normal operating conditions there should be no differential current (although there might be a small
amount due to CT mismatch). Under conditions such as curr
ent transformer (CT) failure or a failure of the CT
circuitry, a small differential current may be seen. This product can monitor the scheme for such conditions with a
dual slope differential characteristic, by enabling the Circuitry Fail setting in the DIFF PROTECTION column. The
characteristic is then defined by the settings Is-cctfail and k-cctfail. By default it is a time-delayed element to
prevent conflict with the tripping characteristic in the event of a genuine transformer fault. But if the ratio of
differential to bias current exceeds the Is-cctfail and k-cctfail settings, but does not exceed the Is1 and k1
settings, for the duration of the Is-cctfail setting, a circuitry fail alarm is raised. The Is-cctfail delay is set to 5
seconds by default.
The level at which the circuitry fail alarm would operate under these circumstances is shown by the red line as
follows:
Ibias /Inom
I
diff/Inom
Is-cctfail
Is1
Is-CTS
I
s-HS1
Is-HS2
Is2
K
1
K2
K-cctfail
Restraint region
O
perate region
V03128
TC and CT errors
Figure 45: Bias characteristic with circuitry fail alarm
P64x Chapter 6 - Transformer Differential Protection
P64x-TM-EN-1.3 115

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE P642 and is the answer not in the manual?

GE P642 Specifications

General IconGeneral
BrandGE
ModelP642
CategoryRelays
LanguageEnglish

Related product manuals