DEFAULT CONFIGURATION IN TRACKSO IOT GATEWAY
Inverter ID: 1, 2, 3, 4 …. Continuous numbering starting with 1, (Range: 1 to 247)
Baud Rate: 9600 (Default) (Values: 9600, 19200, 38400)
Data Bits: 8 , Stop Bit: 1 , Parity: None
CONFIGURATION AT THE INVERTER END
SETTING THE BAUD RATE
Default Baud rate for GoodWe Inverters is 9600bps.
SETTING THE INVERTER ID
The inverter ID is used to identify the inverter in a RS485 connection
Set a different inverter ID for each inverter in the PV plant. Otherwise, the inverters cannot be correctly
identified.
On the last inverter in the RS485 connection, switch on the RS485 termination resistor.
SET DATE & TIME OF INVERTER
For a precise calculation of the statistics in the inverter itself and in a monitoring system, date and time have to be
correct.
Set the Correct Date & Time
Set correct Inverter Ids