EasyManuals Logo

Gree FHBQ-D5-K User Manual

Gree FHBQ-D5-K
39 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
4
Energy-Recovery Ventilation
System Service Manual
QSPEVDU
Model FHBQ-D15-M FHBQ-D20-M FHBQ-D30-M
Code EH01100050 EH01100060 EH01100070
$LUÀRZ9ROXPH H-M-L m
3
/h 1500 2000 3000
External Statics Pressure H-M-L Pa 150 150 220
Temperature
H[FKDQJHHI¿FLHQF\
H-M-L % 73 71 70
Enthalpy
exchange
HI¿FLHQF\
Heating H-M-L % 65 62 62
Enthalpy
exchange
HI¿FLHQF\
Cooling H-M-L % 60 58 58
Recommended
wiring
Quantity 5 5 5
Area mm
2
1.5 1.5 1.5
Power Supply 380~415V 3N~50Hz 380~415V 3N~50Hz 380~415V 3N~50Hz
Power Input W 600 950 2800
Sound Pressure level dB(A) 48 50 54
Outline Dimension (W X D X H) mm 1210X1215X452 1210X1215X452 1340X1550X572
Package Dimension (WX D X H) mm 1550X1540X470 1550X1540X470 1710X1610X700
Net. Weight kg 100 100 240
*URVVZHLJKW kg 115 115 280
/RDGLQJTXDQWLW\
*3 15 15 9
*3 37 37 24
40'HQ 44 44 24
Standard wired remote controller Z5N15 Z5N15 N/A
Note:
1. The models of 220v power supply type has 3types of fan speed and the models of 380V have one fan
speed.
2. 7KHWHPSHUDWXUHH[FKDQJHHI¿FLHQF\DQGHQWKDOS\H[FKDQJHHI¿FLHQF\DUHWHVWHGXQGHUWKHVHWHVWLQJ
conditions as below:
&RROLQJHI¿FLHQF\,QGRRUDLU
ć
DB, 19.5
ć
WB, outdoor temperature 35
ć
DB, 28
ć
WB
.
+HDWLQJHI¿FLHQF\
ć
DB,13
ć
WB. Outdoor air temperature: 5
ć
DB, 2
ć
WB
.
3. Sound power level according to ISO 5151-sound pressure calculated at 1.5m distance.
4. Operation condition:ambient temperature-15
ć
-50
ć
relevate humidity less than 80
ˁ
RH.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree FHBQ-D5-K and is the answer not in the manual?

Gree FHBQ-D5-K Specifications

General IconGeneral
BrandGree
ModelFHBQ-D5-K
CategoryFan
LanguageEnglish

Related product manuals