EasyManuals Logo
Home>Gree>Inverter>GMV-280WM/H-X

Gree GMV-280WM/H-X User Manual

Gree GMV-280WM/H-X
77 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #73 background imageLoading...
Page #73 background image
GMV DC Inverter VRF
69
——
Error
Code
Content
Error
Code
Content
Indoor
oA
Drive IPM high temperature protection of
IDU
ob
Malfunction of drive temperature sensor of
IDU
oC Malfunction of charging loop of IDU o0 Other malfunction of drive
Outdoor
E0
Malfunction of ODU
E1
High-pressure protection
E2
Discharge low-temperature protection
E3
Low-pressure protection
E4
High discharge temperature protection of
compressor
Ed Drive IPM low temperature protection
F0
Main board of ODU is poor
F1
Malfunction of high-pressure sensor
F3 Malfunction of low-pressure sensor F5
Malfunction of discharge temperature sensor
of compressor 1
F6
Malfunction of discharge temperature
sensor of compressor 2
F7
Malfunction of discharge te
mperature sensor
of compressor 3
F8
Malfunction of discharge temperature
sensor of compressor 4
F9
Malfunction of discharge temperature sensor
of compressor 5
FA
Malfunction of discharge temperature
sensor of compressor 6
FC Current sensor of compressor 2 is abnormal
FL
Current sensor of compressor 3 is
abnormal
FE Current sensor of compressor 4 is abnormal
FF
Current sensor of compressor 5 is
abnormal
FJ Current sensor of compressor 6 is abnormal
FP Malfunction of DC motor FU
Malfunction of casing top temperature sensor
of compressor 1
Fb
Malfunction of casing top temperature
sensor of compressor 2
Fd
Malfunction of exit tube temperature sensor
of mode exchanger
Fn
Malfunction of inlet tube temperature
sensor of mode exchanger
J0
Protection for other modules
J1
Over-current protection of compressor 1
J2
Over-current protection of compressor 2
J3 Over-current protection of compressor 3 J4 Over-current protection of compressor 4
J5
Over-current protection of compressor 5
J6
Over-current protection of compressor 6
J7
Gas-mixing protection of 4-way valve
J8
High pressure ratio protection of system
J9 Low pressure ratio protection of system JA Protection because of abnormal pressure
JC
Water flow switch protection
JL
Protection because high pressure is too low
JE
Oil-return pipe is blocked
JF
Oil-return pipe is leaking
b1
Malfunction of outdoor ambient
temperature sensor
b2
M
alfunction of defrosting temperature sensor
1
b3
Malfunction of defrosting temperature
sensor 2
b4
Malfunction of liquid outlet temperature
sensor of sub-cooler
b5
Malfunction of gas outlet temperature
sensor of sub-cooler
b6
Malfunction of inlet tube temperature sensor
of vapor liquid separator
b7
Malfunction of exit tube temperature
sensor of vapor liquid separator
b8 Malfunction of outdoor humidity sensor
b9
Malfunction of gas temperature sensor of
heat exchanger
bA
Malfunction of oil-return temperature sensor
1
bH Clock of system is abnormal bE
Malfunction of inlet tube temperature sensor
of condenser
bF
Malfunction of outlet tube temperature
sensor of condenser
bJ
High-pressure sensor and low-pressure
sensor are connected reversely
bP
Malfunction of temperature sensor of
oil-return 2
bU
Malfunction of temperature sensor of oil
return 3
bb
Malfunction of temperature sensor of oil
return 4
bd
Malfunction of gas inlet temperature sensor
of sub-cooler
bn
Malfunction of liquid inlet temperature
sensor of sub-cooler
P0 Malfunction of driving board of compressor
P1
Driving board of compressor operates
abnormally
P2
Voltage protection of driving board power of
compressor

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-280WM/H-X and is the answer not in the manual?

Gree GMV-280WM/H-X Specifications

General IconGeneral
BrandGree
ModelGMV-280WM/H-X
CategoryInverter
LanguageEnglish

Related product manuals