6
3
UNIT PARAMETERS
3.1 Outdoor Unit
Outdoor Units_Heat Recovery To n 6 8 10
Model - GMV-Q72WM/B-F(U) GMV-Q96WM/B-F(U) GMV-Q120WM/B-F(U)
Module combination - GMV-Q72WM/B-F(U) GMV-Q96WM/B-F(U) GMV-Q120WM/B-F(U)
Performance
Nominal Cooling Capacity
Btu/h 72000 96000 120000
kW 21.1 28.1 35.2
Rated Cooling Capacity Btu/h 67000 90000 111000
Nominal Heating Capacity
Btu/h 81000 108000 135000
kW 23.7 31.7 39.6
Rated Heating Capacity Btu/h 75000 100000 126000
Cooling Power Input kW 5.45 7.30 9.58
Heating Power Input kW 5.80 7.85 10.42
Sound Pressure Level dB(A) 61 62 63
Power Supply - 208/230V 3~ 60Hz
Compressor
Type - Inverter scroll type Inverter scroll type Inverter scroll type
Number N 1 1 2
Motor Output
kW 7.15 7.15 7.15+3.88
Starting Method - Inverter Inverter Inverter
Operating Range - 13%~100% 11%~100% 12%~100%
Refrigeration Oil Brand - FVC68D or FV-68H FVC68D or FV-68H FVC68D or FV-68H
Oil Charge
Compressor L 1.1 1.1 1.1+0.5
Oil separate tank L 4.0 4.0 5.0
Total L 5.1 5.1 6.6
Fan
Type×Quantity - Propeller×2 Propeller×2 Propeller×2
Motor output W 750+750 750+750 750+750
Starting method - Inverter Inverter Inverter
Air ow rate
m
3
/h 14000 14000 14000
cfm 8240 8240 8240
Max. external static pressure
Pa 82 82 82
in.W.G 0.328 0.328 0.328
Ambient
temperature
range
Cooling
°C -5~52 -5~52 -5~52
23~125.6 23~125.6 23~125.6
Heating
°C -20~24 -20~24 -20~24
-4~75.2 -4~75.2 -4~75.2

Other manuals for Gree GMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV5 Series and is the answer not in the manual?

Gree GMV5 Series Specifications

General IconGeneral
BrandGree
ModelGMV5 Series
CategoryInverter
LanguageEnglish

Related product manuals