Gree GMV6 DC Inverter VRF Units Service Manual
Model - GMV-2525WM/G-U GMV-2590WM/G-U GMV-2655WM/G-U GMV-2720WM/G-U
Heating current input A 25.0+25.0+25.0+28.8 25.0+25.0+28.8+28.8 25.0+28.8+28.8+28.8 28.8+28.8+28.8+28.8
Rated power input kW
Rated current A 38+38+38+40.9 38+38+40.9+40.9 38+40.9+40.9+40.9 40.9+40.9+40.9+40.9
Refrigerant type - R410A R410A R410A R410A
Refrigerant charge kg 8.3+8.3+8.3+8.3 8.3+8.3+8.3+8.3 8.3+8.3+8.3+8.3 8.3+8.3+8.3+8.3
unit 80(85)* 80(90)* 80(95)* 80(100)*
Gas pipe mm Φ44.5 Φ44.5 Φ44.5 Φ44.5
Liquid pipe mm Φ22.2 Φ22.2 Φ22.2 Φ22.2
Outline dimensions
(W × D × H)
mm
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690+
Packing dimensions
(W × D × H)
mm
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855+
Net weight kg 355+355+355+360 355+355+360+360 355+360+360+360 360+360+360+360
Gross weight kg 370+370+370+375 370+370+375+375 370+375+375+375 375+375+375+375
NOTICE!:
*The maximum connection quantity of indoor unit in the brace should be engineering
customized.
3 The Range of Production Working Temperature
Ambient temperature
-15℃*(5℉) ~48℃(118.4℉) DB -25℃(-13℉) ~24℃(75.2℉) DB
Indoor temperature
14℃(57.2℉) ~25℃(77℉) WB 15℃(59℉) ~27℃(80.6℉) DB
*
Note: Cooling at -15~ -5
℃
(5~23
℉
) is conditional. Please inquire our engineers for more
information. Generally, the lowest operating temperature for cooling is -5
℃
(23
℉
).
When the indoor units are all VRF fresh air processor, the unit operating range is as follows:
Cooling
Ambient temperature: 16
℃
(60.8
℉)
~45
℃
(113
℉)
Heating
Ambient temperature: -7
℃
(19.4
℉)
~16
℃
(60.8
℉)
If exceeding the temperature range for working, the product may be damaged, which is not within
the warranty range.