Gree GMV6 DC Inverter VRF Units Service Manual
10
Model - GMV-2525WM/G-U GMV-2590WM/G-U GMV-2655WM/G-U GMV-2720WM/G-U
Heating current input A 25.0+25.0+25.0+28.8 25.0+25.0+28.8+28.8 25.0+28.8+28.8+28.8 28.8+28.8+28.8+28.8
Rated power input kW
25.50+25.50+25.50+2
8.50
25.50+25.50+28.50+2
8.50
25.50+28.50+28.50+
28.50
28.50+28.50+28.50+28
.50
Rated current A 38+38+38+40.9 38+38+40.9+40.9 38+40.9+40.9+40.9 40.9+40.9+40.9+40.9
Refrigerant type - R410A R410A R410A R410A
Refrigerant charge kg 8.3+8.3+8.3+8.3 8.3+8.3+8.3+8.3 8.3+8.3+8.3+8.3 8.3+8.3+8.3+8.3
Maximum drive IDU
NO.
unit 80(85)* 80(90)* 80(95)* 80(100)*
Gas pipe mm Φ44.5 Φ44.5 Φ44.5 Φ44.5
Liquid pipe mm Φ22.2 Φ22.2 Φ22.2 Φ22.2
Outline dimensions
(W × D × H)
mm
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690
Packing dimensions
(W × D × H)
mm
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855
Net weight kg 355+355+355+360 355+355+360+360 355+360+360+360 360+360+360+360
Gross weight kg 370+370+370+375 370+370+375+375 370+375+375+375 375+375+375+375
NOTICE!:
*The maximum connection quantity of indoor unit in the brace should be engineering
customized.
3 The Range of Production Working Temperature
Cooling
Heating
Ambient temperature
-15*(5) ~48(118.4) DB -25(-13) ~24(75.2) DB
Indoor temperature
14(57.2) ~25(77) WB 15(59) ~27(80.6) DB
Indoor humidity
≤80%
*
Note: Cooling at -15~ -5
(5~23
) is conditional. Please inquire our engineers for more
information. Generally, the lowest operating temperature for cooling is -5
(23
).
When the indoor units are all VRF fresh air processor, the unit operating range is as follows:
Cooling
Ambient temperature: 16
(60.8
)
~45
(113
)
Heating
Ambient temperature: -7
(19.4
)
~16
(60.8
)
If exceeding the temperature range for working, the product may be damaged, which is not within