Gree GMV6 DC Inverter VRF Units Service Manual
320
Appendix 4 Electric Specifications
Every unit should have corresponding short-circuit and overload protection. And also a main switch
is required to control Power or disconnection.
Please refer to the following table for the leakage protection switch and circuit breaker of outdoor
unit.
Outdoor units Combination
Power Fuse Capacity
Minimum Circuit
Ampacity
Maximum
Overcurrent
Protection
Cross-sectional
Area of Power
—
25 19.6 25
4*4.0
—
25 20 25
4*4.0
—
30 21 30
4*4.0
—
30 23.9 30
4*4.0
—
30 24.2 30
4*4.0
—
30 25 30
4*4.0
—
40 36.2 40
4*6.0
—
40 38 40
4*6.0
GMV-
680WM/G-U
—
3~ 60Hz
45 40.9 45
4*10.0
GMV-
335+400
20+30 21.0+23.9 20+30 4*4.0+4*4.0
335+450
20+30 21.0+24.2 20+30 4*4.0+4*4.0
839WM/G-U
335+504
3~ 60Hz
20+30 21.0+25.0 20+30 4*4.0+4*4.0
280+615
20+40 20.0+38.0 20+40 4*4.0+4*6.0
335+615
20+40 21.0+38.0 20+40 4*4.0+4*6.0
400+615
30+40 23.9+38.0 30+40 4*4.0+4*6.0
504+560
30+40 25.0+36.2 30+40 4*4.0+4*6.0
504+615
30+40 25.0+38.0 30+40 4*4.0+4*6.0
560+615
40+40 36.2+38.0 40+40 4*6.0+4*6.0