EasyManuals Logo
Home>Haskris>Chiller>R Series

Haskris R Series User Manual

Default Icon
11 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
Copyright © 2020 Haskris REV102920
5
www.haskris.com
776 North Oaklawn Avenue, Elmhurst, Illinois 60126 USA ph: +1-847-956-6420 | fx: +1-847-956-6595 | email: service@haskris.com
Operation and Maintenance
Haskris LX-Series, R-Series, WW-Series, OPC-Series
Section 2: Indicator Lights
Section 2.1: ON/OFF or Power
Some units have a green light indicating the unit’s ON/OFF status.
Some units indicate that they are ON by lighting the temperature controller.
Section 2.2: Liquid Level
Some units with a tank have a light to indicate whether the liquid level in the tank is sufcient.
Some units have a “FULL light. This must be lit for the unit to function.
Some units have a “Liquid Level Low” indicator. This must not be lit for the unit to function.
Section 2.3: Liquid Temperature Fault
Some units have a “Liquid Temperature Fault” indicator. This means that the liquid temperature
is above or below the alarm set points.
Section 2.4: Refrigerant Pressure High or Building Water Fault
Some units with a high refrigerant pressure safety switch include either a “High Pressure
Indicator” or a “Building Water Fault” indicator.
Units require either fresh air or a source of cooling water to discharge heat. If ow of fresh air
or cooling water through the condenser is insufcient, refrigerant pressure increases. When the
pressure is too high, a safety switch will stop the unit and light this indicator.
The high pressure switch can be manually reset after the refrigerant pressure decreases to
a safe level. The switch may be located on the base of the chiller or near the condenser. The
switch has a button that can be pressed to reset the switch.
Section 2.5: Refrigerant Pressure Low
In refrigerated units, a low refrigerant pressure switch stops the unit if the compressor suction
line pressure is too low.
This can indicate a refrigerant leak. Contact a local refrigeration technician to repair the leak
and recharge the system with refrigerant.
This indicator may appear on startup. This is normal.
- Turn the system power ON, and wait until the compressor starts.
- Cycle the system OFF and ON 3 to 4 times before permanently switching the system ON.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Haskris R Series and is the answer not in the manual?

Haskris R Series Specifications

General IconGeneral
BrandHaskris
ModelR Series
CategoryChiller
LanguageEnglish

Related product manuals