EasyManuals Logo

Honeywell AQUASTATIC L7224 Series User Manual

Honeywell AQUASTATIC L7224 Series
4 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
TECHNICIAN’S QUICK REFERENCE GUIDE
69-1957—1
L7224 Series
Oil Electronic
Aquastat® Controller
The following service procedure provides a quick overview for
L7224 Series Controllers. For more information, refer to form
69-1384.
On the L7224U the High Limit, High Limit Differential, Low Limit,
and Low Limit Differential can be adjusted to the settings
recommended by the boiler OEM.
Adjusting Settings
To discourage unauthorized changing of Aquastat® settings, a
procedure to enter the adjustment mode is required. To enter the
adjustment mode, press the UP, DOWN, and I buttons
simultaneously for three seconds. Press the I button until the
feature requiring adjustment is displayed:
HL—High Limit.
LL—Low Limit.
Ldf—Low Limit differential.
F - C—°F or °C.
Then press the UP and/or DOWN buttons to move the set point to
the desired value. After 60 seconds without any button inputs, the
control will automatically return to the READ mode.
To use the L7224U in a cold start boiler application, disable the
Low Limit function by pressing the UP arrow button, DOWN arrow
button and I buttons simultaneously for three seconds. Then push
the I button until LL is displayed. Then press the down arrow
button until OFF is displayed.
Display
In the RUN mode, the Aquastat® will flash “bt” (boiler temp)
followed by the temperature (i.e., 220), followed by °F or °C.
To read boiler settings, press the I key to read the parameter of
interest. For example, press I (HL) High Limit is displayed,
followed by a three-digit number, i.e., 220, followed by °F or °C.
69-1957-1.fm Page 1 Tuesday, June 20, 2006 11:06 AM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell AQUASTATIC L7224 Series and is the answer not in the manual?

Honeywell AQUASTATIC L7224 Series Specifications

General IconGeneral
TypeAquastat Controller
ControlOn/Off
Temperature Range100°F to 240°F (38°C to 116°C)
Switching ActionSPDT
ApprovalsUL Listed, CSA Certified
Electrical ConnectionsScrew terminals
Voltage120VAC, 240VAC
DifferentialAdjustable

Related product manuals