DISTRIBUTED I/O
EN0B-0090GE51 R0802 6
Analog Output Module XFL522B
Eight outputs (AO1 – AO8), short-circuit proof
Signal levels 0...10 Vdc
U
max
= 11 Vdc, I
max
= +1 mA, -1 mA
Protected outputs up to 40 Vdc / 24 Vac
8-bit resolution
Zero point < 200 mV
Accuracy ± 150 mV deviation from output voltage
One red LED per channel (light intensity proportional to
output voltage)
Green power LED (L1) and red L
ONWORKS status LED
(L2)
Control updating every 1 sec with CPU
Dimensions (WxLxH): 47x97x70 mm
This analog output module has eight output channels
which can be connected to actuators or other suitable
analog devices.
The unit plugs into the XSL513 Terminal Block and can be
inserted and removed without disturbing other units on the
bus. Terminals AO1 through AO8 are the analog outputs.
Terminals 9 through 17 are connected to ground. Eight red
LEDs are located on top of the module. The brightness of
each LED is proportional to the output level of the cor-
responding channel. The module address is set using the
rotary HEX switch (in the case of applications prior to
CARE 4.0).
Open Loop Actuator
Object Type #3
Mandatory
Network
Variables
input
NV 1
nviRequest
SNVT_obj_request
nv1
nviValue
SNVT_switch
input
NV 1
nviRequest
SNVT_obj_request
nv3
nvoFeedback
SNVT_switch
Optional
Network
Variables
Optional
Configuration
Properties
input
NV 1
nviRequest
SNVT_obj_request
nc1
UCPTSensorConfig
input
NV 1
nviRequest
SNVT_obj_request
nc2
UCPTdriveTimeClose
input
NV 1
nviRequest
SNVT_obj_request
nc3
UCPTdriveTimeOpen
input
NV 1
nviRequest
SNVT_obj_request
nc4
UCPTsyncMin
input
NV 1
nviRequest
SNVT_obj_request
nc5
UCPTsyncMax
input
NV 1
nviRequest
SNVT_obj_request
nc6
UCPTsyncCharge
input
NV 1
nviRequest
SNVT_obj_request
nc88
UCPTminDeltaLevel
input
NV 1
nviRequest
SNVT_obj_request
nc96
UCPTdelayTime
Fig. 3. LONMARK Object for each analog output

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Excel 5000 open XFL523B and is the answer not in the manual?

Honeywell Excel 5000 open XFL523B Specifications

General IconGeneral
BrandHoneywell
ModelExcel 5000 open XFL523B
CategoryI/O Systems
LanguageEnglish

Related product manuals