IF-LON2 – MOUNTING INSTRUCTIONS
Manufactured for and on behalf of the Environmental & Energy Solutions Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
Home and Building Technologies
Honeywell GmbH
Böblinger Strasse 17
71101 Schönaich / Deutschland
Phone: (49) 7031 63701
Fax: (49) 7031 637493
http://ecc.emea.honeywell.com
MU1B-0545GE51 R0117A Subject to change without notice.
Hardware Installation
Using the supplied USB cable, connect the IF-LON2 Interface
to the designated USB-Client port of the Honeywell controller
(see Fig. 1).
NOTE: In performing this action, it is not necessary to
remove the Honeywell controller from power.
1
3
2
4
5
Fig. 1. Connecting the IF-LON2
Table 1. Legend
no. term remarks
1
LonWorks® connector 2-pin: TP/FT-10
2
SERVICE LED (yellow) Indicates Service Pin
Neuron processor activity
3
L
ONWORKS LED Tx/Rx Indicates LONWORKS
communication
4
Service Pin Button Manual activation of a
Service Pin message
5
USB connector Use supplied USB cable
See also IF-LON2 Interface – Installation Instructions (MU1B-
0538GE51) for more-detailed information.
Mounting
The IF-LON2 Interface is suitable for DIN rail mounting:
Fig. 2. DIN rail mounting
1. Angle the IF-LON2 at the upper edge of the DIN rail.
2. Swing the IF-LON2 down and apply gentle force until it
snaps into position with an audible "click."
3. If desired, mount stoppers at the ends of the rail to
prevent sliding.
Technical Specifications
Table 2. Technical specifications
term remarks
Bus interface USB: Micro-B female
USB-conform as per USB
specification 2.0 and 1.1; 12 Mbit/sec
Network interface EIA 709-conform, TP/FT-10
Operating temperature +0 °C to +50 °C
Storage temperature -20 °C to +70 °C
Max. humidity 10 … 95% at +50 °C, non-condensing
Listings CE mark
Operating input voltage 5 VDC (USB power)
Operating input current 110 mA max. (USB power)