MINIPEEPER® ULTRAVIOLET FLAME DETECTORS
3 60-202610
C7035A Minipeeper® Ultraviolet
Flame Detector:
Flame Detection:
End viewing.
Ambient Operating Temperature Ratings:
0°F to 250°F
(-18°C to +121°C), or -40°F to 250°F (-40°C to +121°C),
depending on model.
Maximum Pressure Rating:
5 psi (34.5 kPa).
Mounting:
Collar with 1-11-1/2 NPSM internal threads for
mounting on a 1 in. sight pipe. (The DIN approved
C7035A1064 has 1-11 BSP.P1 threads.)
Wiring Connections:
Two 6 ft. [1.83 m], color-coded NEC
Class 1 leadwires rated for 302°F (150°C). One model is
available with 12 ft. (3.66 m) leadwires. Rear of detector
has 1/2-14 NPSM internal threads for connecting to a
conduit. The DIN-approved C7035A1064 has 1/2-14
BSP-F threads.
C7035A1056 has 12 ft (3.66 m) leadwires.
C7035A1080 leadwire is rated for 600°F (204°C).
Dimensions:
See Fig. 2.
Replacement Parts:
129808 Flange Gasket.
129464M Ultraviolet Sensing Tube, 0°F to 250°F (-18°C to
+121°C).
129464N Ultraviolet Sensing Tube, -40°F to +250°F (-40°C to
121°C).
C7027A AND C7035A:
Approvals:
Underwriters Laboratories Inc. listed: File No. MP268.
Canadian Standards Association certified: Master Report LR
95329-1.
Factory Mutual approved.
Industrial Risk Insurers acceptable.
DIN approved models: C7027A1056, C7035A1049,
C7035A1064.
Accessory:
118367A Swivel Mount; provides adjustable
positioning of the C7027A or C7035A.
Fig. 3. Installation dimensions of C7044A in in. (mm).
C7044A Minipeeper® Ultraviolet
Flame Detector:
Flame Detection:
Housing has two openings to permit either
side or end viewing. Side viewing is 1/8 as sensitive as end
viewing.
Mounting:
Bracket (included in 4074BVK Bag Assembly),
secured by two 8-32 RHIS (European M-4) screws (not
included).
Wiring Connections:
Two 6 ft. (1.83 m) color-coded NEC
Class 1 leadwires. Rear of detector has a clamp type
connector for 1/2 in. flexible metallic conduit.
Dimensions:
See Fig. 3.
C7927A Minipeeper® Ultraviolet
Flame Detector:
Ambient Operating Temperature Ratings:
C7927A1016 (U.S. Version): -40°F to +200°F (-40°C to
+93°C).
C7927A1008 (European Version): -4°F to +140°F
(-20°C to +60°C).
Storage Temperature Rating:
-20°F to +120°F
(-28°C to +49°C).
Maximum Pressure Rating:
5 psi 34.5 kPa).
Mounting:
Collar with 1/2-14 NPSM internal threads for
mounting on a 1/2 in. (13mm) sight pipe.
Wiring Connections:
Two four-foot (1.2 meter) color-coded
NEC Class 1 leadwires. Rear of detector has a clamp-type
connector for 1/2 in. (13mm) flexible metal conduit.
Dimensions:
See Fig. 4 and 5.
Approvals:
Underwriters Laboratories Inc. (UL): Pending.
Factory Mutual (FM): Pending.
IAS: Pending.
MOUNTING BRACKET
6 FOOT [1.83 METER]
LEADWIRES (2)
M1944B
3-5/8 (92)
1/2
(13)
9/16
(14)
7/8
(22)
3/8
(10)
1-27/64
(36)
C7044

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Minipeeper C7027A and is the answer not in the manual?

Honeywell Minipeeper C7027A Specifications

General IconGeneral
BrandHoneywell
ModelMinipeeper C7027A
CategorySecurity Sensors
LanguageEnglish

Related product manuals