Display Features
• Large LCD Display: 640 characters (16 lines x 40
characters) with long-life LED backlight
• Program keypad: full QWERTY keypad for field
programmability
• UserControl:Up to nine users, each with a password
and selectable access levels
• LED indicators: Fire; Pre-Alarm; Fault; Disable;
Supervisory; Other Event; System Fault; Alarm Routing
Equipment Status; Alarm Devices Status; Smoke Control
Status; Controls Active
• Membrane Switch Controls: Silence Buzzer; Silence/
Re-sound Alarm; Scroll Alarms; Reset; Disable
Flashscan® Intelligent Features
Polls up to 318 devices on each loop in less than two
seconds
Activates up to 159 outputs in less than five seconds
Multicolor LEDs blink device address during Walk Test
Fully digital, high-precision protocol
Manual sensitivity adjustment - up to nine levels
Pre-alarm ONYX intelligent sensing - up to nine levels
Sensitivity levels:
- Ionization – 0.3 to 0.6 MIC X
- Photo electric – 2.0 to 8.0%/metre obscuration
- Laser (VIEW®) – 0.07 to 6.4%/metre obscuration
- Acclimate Plus™ – 2.0 to 10.0%/metre obscuration
- IntelliQuad™– 1.6 to 12.5%/metre obscuration
Drift compensation
Multi-detector algorithm involves nearby detectors in
alarm decision
Automatic detector sensitivity testing
Maintenance alert (two levels)
Self-optimizing pre-alarm
Programmable activation of sounder/relay bases during
alarm or pre-alarm
Read Status displays the level of detector cleanliness
FSP-851AUS
Photoelectric Smoke Sensor
Advanced ONYX intelligent sensing including automatic
drift compensation to reduce unwanted alarms and
provide warning of contamination build-up
Addressable operation pinpoints the fire location
Protection against the entry of insects and other
contaminants
FAPT-851AUS Acclimate Plus™
Intelligent Multi-Criteria Detector
Detector automatically adjusts sensitivity levels without
operator intervention or programming. Sensitivity
increases with heat
Microprocessor-based technology; combination photo
and thermal technology
FSC-851AUS IntelliQuad™
Advanced Multi-Criteria Detector
Detects all four major elements of a fire (smoke, heat,
CO, and flame)
Automatic drift compensation of smoke sensor and CO
cell
High nuisance-alarm immunity
FSL-751 VIEW® (Very Intelligent Early Warning)
Smoke Detection Technology
Advanced ONYX intelligent sensing algorithms
differentiate between smoke and non-smoke signals
Addressable operation pinpoints the fire location
Early warning performance comparable to the best
aspiration systems at a fraction of the lifetime cost
FST-851(R)-WP
Sealed Thermal Sensor
Suitable for harsh environments with wide operating
temperature and sealed to IP67
Addressable operation pinpoints the fire location and
annunciates alarm with dual LEDs
FMM-4-20 Interface Module
Interface to industry standard linear scale 4-20mA
sensors
Five programmable thresholds
Voice Evacuation Features
Up to eight channels of digital audio when using DVC
50 watt digital amplifiers (DAA2 series)
30/60/120 watt digital amplifiers (DA Series)
Solid state message generation
Hard-wired voice control module options
Backup tone generator and amplifier option