Page 2 of 7 — DN-60637:N • 9/15/2022
FLASHSCAN
®
INTELLIGENT FEATURES
• Polls up to 318 devices in less than two seconds.
• Activates up to 159 outputs in less than five seconds.
• Multicolor LEDs blink device address during Walk Test.
• Fully digital, high-precision protocol (U.S. Patent 5,539,389).
• Manual sensitivity adjustment — up to nine levels.
• Pre-alarm ONYX intelligent sensing — up to nine levels.
• Day/Night automatic sensitivity adjustment.
• Sensitivity levels:
–Photo – 0.5 to 2.35%/foot obscuration.
– High-Sensitivity Photoelectric (VIEW
®
) – Open Air Protection
(0.5% - 2.0%/ft. obscuration), Special Applications (0.02%-
0.5%/ft. obscuration)
– Multi-Criteria Detector – Open Air Protection (2.52-3.89%/ft.
obscuration), Special Applications (1.13-2.52%/ft. obscuration)
• Drift compensation (U.S. Patent 5,764,142).
• Degraded mode: In the unlikely event that the
CPU-320SYS
microprocessor fails, FlashScan detectors revert to degraded
operation and can activate the control panel’s NAC circuits and
alarm relay. Each of the four built-in panel circuits includes a Dis-
able/Enable switch for this feature.
• Multi-detector algorithm involves nearby detectors in alarm deci-
sion (U.S. Patent 5,627,515).
• Automatic detector sensitivity testing (NFPA-72 compliant).
• Maintenance alert (two levels).
• Self-optimizing pre-alarm.
SWIFT WIRELESS
• Self-healing mesh wireless protocol.
• Each SWIFT Gateway supports up to 49 SWIFT devices.
• Up to 4 wireless gateways can be installed with overlapping net-
work coverage.
RELEASING FEATURES
• Ten independent hazards.
• Sophisticated cross-zone (three options).
• Delay timer and Discharge timers (adjustable).
• Abort (four options).
• Low-pressure CO
2
listed.
VOICE FEATURES
• Integrates with FirstCommand Series. See DN-60772.
• Telephone applications require NFC-FFT.
HIGH-EFFICIENCY OFFLINE SWITCHING
3.0 A P
OWER SUPPLY (6.0 A IN ALARM)
• 120 VAC (NFS-320/NFS-320C); 240 VAC (NFS-320E).
• Displays battery current/voltage on panel (with display).
FSV-951 SERIES VIEW
®
(VERY INTELLIGENT EARLY WARNING)
H
IGH-SENSITIVITY SMOKE DETECTOR
• Advanced ONYX intelligent sensing algorithms differentiate
between smoke and non-smoke signals.
• Addressable operation pinpoints the fire location.
• Ivory models (-IV) support CLIP mode as well as FlashScan.
• ULC listed models available; “A” models are ULC Listed.
• -R is retrofit, backwards compatible for use with older panels.
FCO-951/-IV ADVANCED MULTI-CRITERIA FIRE/CO DETECTOR
• Detects all four major elements of a fire (smoke, heat, CO, and
flame).
• 135°F (57.2°C) fixed-temperature heat detector.
• Transmits an alarm signal due to heat.
• Separate signal for life-safety CO detection.
Sample
System
Options
NFS-320SYSdia1-2022.wmf
SLC Intelligent Loop 1
DEVICES
FPTI-951
FSP-951
FST-951
FCO-951
…etc.
NBG-12LX
FMM-1
IDC
FDU-80
Up to 32 remote displays
EIA-485
EIA-485
EIA-232
2048 annunciator/control points
Optional 318-point UDACT
Dual phone
lines to
Central
Station
ACM/AEM-24AT
LED Annunciator
LDM-32
Custom Graphics
ACM-8R
Relay Control
FCM-1
NAC
FRM-1
Relay Contact
KDM-R2
display
OR
NFS-320SYS
“C” cabinet size shown
LCD2-80
PRN Series Printer
FWSG(A)
XP6/10 I/O Modules