1. INTRODUCTION
SensePoint is for the detection of toxic gases and is
designed for use with an approved junction box.
It employs an electrochemical cell sensor device which is
gas specic and used as part of a 4-20mA loop powered
measuring circuit. The sensor includes a voltage clamp
within a sealed Exd enclosure and an electrochemical cell
driver and cell within an IS portion of the sensor.
Different sensor versions detect different gases. Sensors
are available for the detection of H
2
S, CO, CI
2
, NH
3
, H
2
, SO
2
,
NO, NO
2
, O
2
. The sensor is available in M20* or 3/4 NPT
thread versions. All accept accessories from the specied
range. Should you require information outside the scope of
these instructions please contact Honeywell Analytics Ltd.
This product is certied for use in hazardous areas and is
protected against water and dust ingress to IP65, or IP66/67
if approved weather protection is tted.
*NOTE - M20 thread option awaiting certication.
2. ASSOCIATED DOCUMENTATION
2106M0502 SensePoint Technical Handbook.
Refer to the relevant control system manual for connection
information.
1. INTRODUCTION & 2. ASSOCIATED DOCUMENTATIONCONTENTS
1. INTRODUCTION .........................................................2
2. ASSOCIATED DOCUMENTATION ..............................2
3. SAFETY ......................................................................3
3.1 Warnings ...........................................................3
3.2 Precautions .......................................................3
4. OPERATIONS .............................................................4
4.1 Installation ........................................................4
4.2 Calibration.........................................................5
4.3 Fault nding ......................................................8
5. MAINTENANCE ..........................................................9
5.1 Changing the electrochemical cell and
internal lter ......................................................9
5.2 Changing the external hydrophobic assembly . 10
Appendix A - Specications .............................. 11
Appendix B - Glossary ......................................12
Appendix C - Main features............................... 13
Appendix D - Spare parts .................................. 14
APPENDIX A - SPECIFICATIONS APPENDIX B - GLOSSARY APPENDIX C - MAIN FEATURES APPENDIX D - SPARE PARTS
Operating temperature range:
see table 1.
Operating humidity range:
20% to 90% RH continuous.
10% to 99% RH intermittent - non condensing.
Operating pressure range:
90 to 110 k Pa.
Warm up time:
see table 1.
Voltage range:
18 to 30 V at sensor.
Power consumption:
0.9 W Max.
Signal output:
4 to 20 mA loop powered.
Calibration ow rate:
recommended between 0.5 and 1.5 l/min.
Expected operating life:
H
2
S, CO, no less than 24 months.
NH
3
, Cl
2
, H
2
, SO
2
, NO
2
, NO, O
2
no less than 12 months.
IP rating:
IP65 standard.
IP66/67 when tted with appropriate weather protection.
Certication:
Ex II 2G EEx dia IIC T4 -55 to +65°C.
Sensepoint 2106AXXXX (Tox).
Vmax 32V BAS98ATEX2157X.
UL approved via IEC 79 (pending).
This product complies with the relevant CE standards
concerning performance: EMC to BS EN50081 parts 1 & 2,
BS EN50082 parts 1 & 2 and EN 45544.
Exd
Flame proof or explosion proof within the connes of European
standards EN50014 and EN50018. An enclosure that can
withstand the pressure developed during the internal explosion
of an explosive mixture and which prevents transmission of
the explosion to the explosive atmosphere surrounding the
enclosure.
Exe
Increased safety within the connes of European standards
EN50014 and EN50019 applied to electrical apparatus that
does not produce arcs or sparks in normal service, in which
additional measures are applied so as to give increased
security against the possibility of excessive temperatures.
PPS
Polymer polyphenylene sulphide, suitable for use in most
chemical environments (eg acids, aldehydes, ketones,
alkalies, petroleum, aromatic hydrocarbons, alcohols, ethers,
esters and most chlorinated hydrocarbons). Avoid immersion
in solvents for extended periods. For further details contact
Honeywell Analytics Ltd.
IS
Intrinsically safe, apparatus in which the circuits themselves
are incapable of causing ignition of a ammable gas.
Replacement sensing elements (including hydrophobic barrier):
gas type replacement cell
O
2
2106B1545
SO
2
2106B1546
Cl
2
2106B1547
CO 2106B1548
H
2
S 2106B1549
NO 2106B1594
NH
3
(1000ppm) 2106B1595
NH
3
(50ppm) 2106B1596
H
2
(1000ppm) 2106B1597
H
2
(10000ppm) 2106B1598
NO
2
2106B1599
Weather protection .........................................02000-A-1635
Flow housing (standard) .................................02000-A-1645
Flow housing (for adsorbent gases) ................02000-A-3120
Junction box (standard) ..................................00780-A-0100
To reorder a complete new sensor, see the label on the product
leads, or contact Honeywell Analytics Ltd.
103mm
Standard Honeywell
Analytics junction box
threads available:
M20*; 3/4” NPT.
SensePoint Toxic
Gas Sensor
Weight - 185g
(205g oxygen)
#
External Hydrophobic barrier
Plastic retainer
103mm
90mm
56mm
52mm
(across ats)
Exe/Exd gland
#
optional
(recommended
for harsh/dirty
environments)
Poole Dorset
SensePoint
static risk - read manual
EEx d ia IIC T4 Tamb -55 +65
o
C
0600
Bas98ATEX2157X II 2G
manufacturer’s
trademark &
address
CE mark
- conforms to
all applicable
European
directives
product name
test house
trademark
certication code
as EN50014 1992
certication number
certied ambient
temperature
range
explosion
protection mark
and equipment
group & category
ident.
number
of ATEX
notied
body
caution
Certication label as dened in directive 94/9/EC
Ser.No./year of manufacture
Operating Instructions
Sensepoint
Toxic Sensor
Contact Honeywell Analytics:
Find out more
www.honeywellanalytics.com
Europe, Middle East, Africa, India
Life Safety Distribution AG
Wilstrasse 11-U31
CH-8610 Uster
Switzerland
Tel: +41 (0)44 943 4300
Fax: +41 (0)44 943 4398
gasdetection@honeywell.com
Americas
Honeywell Analytics Inc.
405 Barclay Blvd.
Lincolnshire, IL 60069
USA
Tel: +1 847 955 8200
Toll free: +1 800 538 0363
Fax: +1 847 955 8208
detectgas@honeywell.com
www.honeywell.com
Technical Services
ha.emea.service@honeywell.com
Asia Pacific
Honeywell Analytics Asia Pacific
#508, Kolon Science Valley (I)
187-10 Guro-Dong, Guro-Gu
Seoul, 152-050,
Korea
Tel: +82 (0)2 2025 0300
Fax: +82 (0)2 2025 0329
analytics.ap@honeywell.com
Please Note:
While every effort has been made to ensure
accuracy in this publication, no responsibility
can be accepted for errors or omissions. Data
may change, as well as legislation, and you
are strongly advised to obtain copies of the
most recently issued regulations, standards,
and guidelines. This publication is not
intended to form the basis of a contract.
Issue 08 08/2008
H_MAN0527_2106M0514
08/08
© 2008 Honeywell Analytics

Other manuals for Honeywell Sensepoint

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Sensepoint and is the answer not in the manual?