5860/5860R
Remote Fire Annunciator
Product Installation Document
Document 151042:E 2/15/2022 ECN: 151062
1 Description
The 5860 (gray) and 5860R (red) are optional 4x20 remote annunciators
that can be surface or flush-mounted.
2 Compatibility
The 5860/R is compatible with Honeywell Silent Knight FACPs. For
more information, see the FACP Installation manual.
3 Specifications
4 Installing the 5860/R
5860/R installation involves the following steps:
1. Ensure power is turned off at the panel.
2. Mount the 5860/R in the desired location.
3. Connect the 5860/R to the panel (see Figure 5).
4. Use the DIP switches on the back of the 5860/R to assign an ID
number. See the FACP Manual for more details.
5. The new 5860/R module must be added to the system through
programming. The JumpStart
®
Auto-programming feature will add
the module automatically. Refer to the FACP Manual for more
information.
5 Mounting
The 5860/R comes from the factory fully assembled. You must disas-
semble it for mounting. To disassemble the annunciator, use a 5/64” hex
wrench to remove the set screws, located on the bottom of the annuncia-
tor bezel.
Figure 1 5860/R Remote Annunciator
Parameter Value
Operating Voltage: 24 VDC
Current Standby: 58 mA
Alarm: 68 mA
Operating Temperature: 0° to 49° C (32° to 120° F)
1".25
(3.175cm)
6.44"
(16.35cm)
8" (20.64cm).125
7".375
Figure 2 Annunciator Dimensions
backbox bezel
side
view