Function
Due to temperature changes the resistance of temperature sensor will be changed. These change of resistance is changing proportional to the
temperature and can be evaluated accordingly.
Remarks:
Select the appropriate temperature sensor with regard to scale range, performance and specific measurement conditions prior to instal-
ling and starting the refrigeration system.
Please make sure that the temperature sensor is only used within the valid measuring range
More Technical Details:
Type TS – NFN TS – NFR TS – RFH
Element Type NTC 10K 1% BETA 3435 NTC 10K BETA 3977 tolerance ± 0,2 °C PT 1000 Class A
Cable Type Thermical rubber poly. Thermical rubber poly. Thermical rubber poly.
Cable colour Black Yellow Green
Cable diameter 2x0,25 mm² Ø 3,3 mm 2x0,25 mm² Ø 3,3 mm 2x0,25 mm² Ø 3,3 mm
Connection Pins Pins Pins
Filling Polyuretanic resin Polyuretanic resin Polyuretanic resin
T
pe Description
Temperature Sensor
TS NFN
Type
Type:
NFN = NTC 10K 1% Beta 3435
NFR = NTC 10K Beta 3977 ±0,2°C
RFH = Pt 1000 class A
Assembl
Position the temperature sensor on the refrigerant pipe in the position between 10 and 14 o'clock (at horizontal pipe installation).
Pay attention to install sensor to clean and intact surfaces at the measuring point.
Provide sufficient thermal compound at the measuring point between temperature sensor and measuring surface.
Fasten the temperature sensor by means of aluminum tape and/or fastening clips to the refrigerant pipe.
Insulate the fastened temperature sensor with heat insulation material.
Connect the temperature sensor according to the instructions of the evaluating equipment.
Ensure that no humidity may enter at cable-ends.
KAT-TS-001
Manufactured for and on behalf of the
Environmental and Combustion Controls
Division of Honeywell Technologies Sàrl,
1180 Rolle, Z.A. La Pièce 16, Switzerland
b
its Authorized Re
resentative Hone
well GmbH
Electrical
Connections
Connection of Temperature Sensors according below picture. Tempe-
rature Sensor is insensible against reverse polarity. TS Sensors have
a 2-wire structure. To minimize electromagnetic perturbation the cable
should be as short as possible.
Automation and Control Solutions
Honeywell GmbH
Hardhofweg
74821 Mosbach/Germany
Phone: +49 (0)
62 61 / 81-475
Fax: +49 (0)
62 61 / 81-461
E-Mail: cooling.mosbach@honeywell.com
www.honeywell-cooling.com