DDSU666-H Smart Power Sensor
User Manual
3 System Maintenance
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
12
Fault phenomenon
Factor analysis
Elimination method
Inaccurate for energy
metering
1. Incorrect wiring, please
check whether the
corresponding phase
sequence of voltage and
current is correct.
2. Check whether the high
& low end of current
transformer inlet is
reversely connected.
Please observe the power
of Pa, Pb, Pc, to be
abnormal if any negative
values.
If the wiring mode is
incorrect, please connect
based on the correct wiring
mode (see the wiring
diagram).
Contact the installation vendor if all failure analysis procedures listed above are completed and the fault
still exists.

Other manuals for Huawei DDSU666-H

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei DDSU666-H and is the answer not in the manual?

Huawei DDSU666-H Specifications

General IconGeneral
Max. Current80 A
Frequency50 Hz
Storage Temperature-40°C to +70°C
CommunicationRS485
Accuracy ClassClass 1
Protection ClassIP51
Rated Voltage230V AC
Voltage Range176 V - 276 V
Rated Current5 A
Operating Temperature-25 °C ~ +60 °C
MountingDIN rail
TypeSingle phase energy meter