Page #1 background image
120-334E-R1
| 1
Note
Ifconvertingtopropane,orderthePropaneConversionPartskit(IBCPart#P-1201)fromyourauthorizedIBC
distributor.
UsetheNaturalGasConversionkitifthefuelsourceatthesiteusesnaturalgasandthemodulatingboilerhasbeenset
up(factoryfire-tested)tooperatewithpropane.Checktheratingplateontheboilertoseewhichfuelsourcetheparticular
boilerhasbeensetupwith.
Usingthisconversionkit,aqualifiedtechnicianwillneedto:
1. Performafuelconversion.
2. Performacombustiontest.
3. Fillintheinformationrequiredonthefuelconversionlabels,andaffixthemtotheboileraftertheconversionis
completed.
Warning
Thisconversionkitshallbeinstalledbyaqualifiedserviceagencyinaccordance
withthemanufacturersinstructionsandallapplicablecodesandrequirementsof
theauthorityhavingjurisdiction.Iftheinformationintheseinstructionsisnot
followedexactly,afire,anexplosionorproductionofcarbonmonoxidemayresult
causingpropertydamage,personalinjuryorlossoflife.
Thequalifiedserviceagencyisresponsiblefortheproperinstallationofthiskit.The
installationisnotproperandcompleteuntiltheoperationoftheconvertedappliance
ischeckedasspecifiedinthemanufacturersinstructionssuppliedwiththekit.
Theboilerwillautomaticallyde-ratethemaximuminputatarateofapproximately2%per1,000'above4,500'.Thegas
valveszerogovernorwillensurethatthegas-airmixtureisnotaffectedataltitude.
Includedwiththeconversionkit:
1xNGMixerAssembly-IBCPart#180-254 4xHexboltM6x14SS-IBCPart#150-373
1xO-ringgasvalvecoupler-IBCPart#150-001 1xRatingPlateFuelOverlay-IBCPart#080-285A
4xHexboltM5x25IBCPart#150-354 1xGasValveConversionLabel-IBCPart#080-107B
4xFlatWasher,0.562ID-IBCPart#150-025 1xInstallerIdentifierLabel-IBCPart#080-283A
4xM6FlatWasherIBCPart#150-159 6xHexboltM8x14-IBCPart#150-329
6xM8Flatwasher-IBCPart#150-339 1xO-ringEBMblower-IBCPart#150-376
Thisconversioninvolveschangingthemixingassembly.
EX 700 - Fuel Conversion to Natural Gas
(LP to NG) P-Kit 1200