Table 1. Features and specifications (continued)
Video controller:
v Matrox G200eV video on system board
v Compatible with SVGA and VGA
ServeRAID SAS controller:
v ServeRAID-BR10i SAS/SATA Controller
that supports RAID levels 0, 1, 1E
(standard)
v Upgradeable to ServeRAID-MR10i
SAS/SATA Controller, which supports
RAID levels 0, 1, 5, 6, 10
v Upgradeable to ServeRAID-MR10is
SAS/SATA Controller, which supports
RAID levels 0, 1, 5, 6, 10
Acoustical noise emissions:
v Sound power, idle: 5.5 bel declared
v Sound power, operating: 6.0 bel
declared
Environment:
v Air temperature:
Server on: 10°C to 35°C (50°F to
95°F); altitude: 0 to 915 m (3000 ft)
Server on: 10°C to 32°C (50°F to
90°F) altitude: 915 m (3000 ft) to
2134 m (7000 ft)
Server on: 10°C to 28°C (50°F to
83°F) altitude: 2134 m (7000) to
3050 m (10000 ft)
Server off: 5°C to 45°C (41F° to
113°F);
Shipping: -40°C to 60°C (-40F° to
140°F);
v Humidity:
Server on: 20% to 80%, Max Dew
Point 21°C, Max. rate of change
5°C/hr
Server off: 8% to 80%, Max. Dew
Point 27°C
Heat output:
Approximate heat output:
v Minimum configuration: 2013 Btu per
hour (590 watts)
v Maximum configuration: 3610 Btu per
hour (1058 watts)
Electrical input:
v Sine-wave input (50-60 Hz) required
v Input voltage low range:
Minimum: 100 V ac
Maximum: 127 V ac
v Input voltage high range:
Minimum: 200 V ac
Maximum: 240 V ac
v Approximate input kilovolt-amperes
(kVA):
Minimum: 0.60 kVA
Maximum: 1.10 kVA
Notes:
1. Power consumption and heat output
vary depending on the number and type
of optional features that are installed
and the power-management optional
features that are in use.
2. These levels were measured in
controlled acoustical environments
according to the procedures that are
specified by the American National
Standards Institute (ANSI) S12.10 and
ISO 7779 and are reported in
accordance with ISO 9296. Actual
sound-pressure levels in a given
location might exceed the average
stated values because of room
reflections and other nearby noise
sources. The declared sound-power
levels indicate an upper limit, below
which a large number of computers will
operate.
Chapter 1. The System x3500 M2 server
7

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBM System x3500 M2 Type 7839 and is the answer not in the manual?

IBM System x3500 M2 Type 7839 Specifications

General IconGeneral
BrandIBM
ModelSystem x3500 M2 Type 7839
CategoryServer
LanguageEnglish

Related product manuals