)ftrEFrMATrc'
Type 1
IMPORTANT
SAFEW
I NSTALLATION I NSTRUCTIONS
Model AG3000
or Type 2
Surge
Protection Device
(SPD)
INSTRUCTIONS
.
SAVE THESE
INSTRUCTIONS
Risk
of
Fire
or
Electric
Shock
.
Disconnect
power
at the
circuit
breaker(s)
or disconnect switch(es) before installing or servicing.
o
Intended for indoor
or outdoor
use.
o
Installation
and/or
wiring must
be
in
accordance
with national
and
local
electrical code and/or Canadian Electrical Code requirements.
.
Installation
and service
to
be
performed
by a
qualified
licensed technician
or electrician.
.
Suitable
for
use on a circuit
capable
of delivering
not more than 20,000
rms symmetrical amperes.
.
This
unit contains
no
serviceable oads.
Risque
d'incendie ou
de choc 6lectrique
.
finstallation
eVou
le
cAblage
doivent
Ctre conformes aux exigences du code de l'6lectricite local en vigueur
eVou du Code
canadien de l'6lectricit6.
!
Uinstallation
et
I'entretien
doivent
6tre
effectu6s
par
Lrn
techojcien
ou 6lectricien
q,"lalifir-
o
Convient
d un circuit capable de
fournir PAS
plus
de
20
000
A
efficaces sym6triques.
.
Cet appareil ne
contient
aucune
pidce
r6parable.
.
Thoroughly
read instructions before installing SPD Unit
.
This
product
does not
protect
against lightning
strikes.
Type 1 installation:
A typical installation
of a
type
1 SPD will be connected between the
secondary
of the service transformer
and
the line
side of
the
service
panel.
This installation
is intended to be installed without
overcurrent
protection
to the SPD.
1. Determining location:
o
Ensure
conductor lengths are as shoft and straight
as
possible
for
best
pedormance.
Do not coil excess wire. The
SPD functions
best
if
all bends in wires are rounded, ideally
to a 4" radius. Hard
90 degree bend will
reduce
efficiency.
Cut all leads to the correct length. Do not
coil excess leads.
2. En5aire
e[ mouritin
g
a?xl conneEti6ns
are' cor6dt and sec-uie.
Once energized
the
green
indicator LED will be
ON
and visible
through the
cover of the SPD.
fype 2 installation:
Atypical installation
of atype2 SPD will be connected tothe load
side
of the service
panel
and
is intended
to be installed with
overcurrent
protection
to
the SPD.
1. Determininglocation:
.
Ensure
conductor
lengths
are as short and straight
as
possible
for best
performance.
Do not
coil excess wire. The
SPD functions best if
all bends
in wires
are rounded, ideally
to a 4" radius. Hard
90 degree bend will reduce efficiency.
Cut
all
leads to the
correct length. Do not coil excess leads.
o
Install
appropriate weatherproof fittings if the
unit is to be
mounted outside.
2. Connect the white wire
from the SPD to the neutral
bus bar in
the
panel
as shown.
.
Connection may also be made to the neutral/ground
bus
bar
if
panel
does
not have
a separate
ground
bus
bar.
3. Connect the two black wires
to a circuit breaker as shown.
For
best
performance
from SPD the maximum recommended
circuit breaker size of 240 VAG,up to
30 A, 2-pole should
be
used.
4. Ensure all mounting
and electrical connections are
correct and
securely fastened. Once
energized the
green
indicator LED will
be ON and visible through
the cover
of
the
SPD.
AG Disconnect
Installation
1. To be installed with
over current
protection
up to 60 A.
Maintenance:
.
AC Voltage
SPD:
o
Periodically
check SPD to ensure
green
indicator
LED is ON.
lf
green
LED
is
OFf,"protection has
diminished and the SPD
should be replaced immediately.
Type 2Installation
Main Breaker
2-Pole, 2O A circuit
breaker shown
A=Black
(Line)
B=Black
(Line)
C=Neutral
(White)