TEC1100 Series Thermostat Technical Bulletin 5
Table 4: Applications
Application Recommended Model
Fan Coil Unit
TEC1101-1
Heat Pump
TEC1102-1
Unit Heaters
TEC1101-1
Packaged Rooftop
TEC1103-1 and Separate Economizer Package
(M130EAA-2 or equal in place of Stage 1). Refer to the
AD-DME1702-1 Direct Mount Economizer Controller
Technical Bulletin (LIT-6363020).
Packaged Heating/Cooling
TEC1101-1 or TEC1103-1
The tools needed to install the TEC1100 Series thermostats are:
•
drill
•
3/16 in. drill bit
•
1/8 in. and 1/4 in. flat-blade screwdrivers
•
hammer
•
marking pencil
•
wire stripper
Note: Two plastic anchors with screws and the cover lock are included
with the TECs.
Mount the TEC1100 Series thermostat on an interior wall, approximately
1.5 m (5 ft) above the floor in a location of average temperature (72°F).
Do not mount the thermostat on outdoor walls or behind doors. Be sure to
install the thermostat away from direct sunlight or radiant heat, air
discharge grills, stairwells, or outdoor doors. Keep the thermostat away
from steam or water pipes, warm air stacks, areas with no airflow, or
sources of electrical interference.
To mount:
1.
Lift the thermostat cover and insert a small coin into the slot located in
the bottom center of the thermostat case.
2.
Twist 1/4 turn (Figure 2).