TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions 9
Table 2: MS/TP Bus Objects (Part 1 of 4)
Point Name Thermostat Point
(Type/Address)
Range
Room Temp
1, 2
AV 6 -40.0°F/-40.0°C to
122.0°F/50.0°F
Room Temp Override
3
BV 7 0 = Normal
1 = Override
Outdoor Temperature
3, 4
AV 8 -40.0°F/-40.0°C to
122.0°F/50.0°F
Sequence of Operation
3
MSV 39 1 = Cooling Only
2 = Heating Only
3 = Cooling and Reheat
4 = Heating and Reheat
5 = Cool/Heat Four-Pipe
6 = Cool/Heat Four-Pipe and Reheat
System Mode
3
MSV 13 1 = Off
2 = Cool
3 = Heat
4=Auto
Occupancy
3
MSV 12 1 = Resume Schedule
2 = Occupied
3 = Unoccupied
4 = Temporary Occupied
PI Heating Demand
5
AV 54 0 to 100%
PI Cooling Demand
5
AV 55 0 to 100%
Supply Temperature
5
AI 11 -40.0°F/-40.0°C to
122.0°F/50.0°F
AUX (BO5) Status
5
BI 65 0 = Off
1=On
AUX (BO5) Output
3
BV 47 0 = Off
1=On
Heating (BO3 and BO4) Valve Status
(TEC2627-2 Model)
5
MSV 66 For On/Off Control:
1=Open
2 = Closed
For Floating Control:
1 = Stopped
2=Opening
3=Closing