Kodiak Recirculating Chiller Technical Manual
Manual # 820-0109, Rev. Y, 07/08/10 - 15 - Check Lytron’s website www.Lytron.com
for the most current technical information.
RS-232 Serial Port Communication
This option allows control of the chiller via a standard 9 pin serial port connected to a computer. Lytron
software is available that simulates the front control panel and all its functions. Alternatively, software can be
created to interface with the system described in the section labeled Host Interface Data Link.
Water Cooled Condenser RC011, RC022, RC030 and RC045
This feature replaces the standard condenser and fan with a water-cooled condenser. This requires cooling
water to be supplied to the chiller at 75F (25C). The facility water pressure must be less than 100 psi.
Minimum flow rates are as follows:
Model Flow Rate (min)
RC011 1.4 gpm
RC022 1.4 gpm
RC030 1.9 gpm
RC045 3.4 gpm