BALTIC R410A-IOM-0708-E Page 90
Low Heat Injection Pressure Checks
Switch the control to Low Heat
Check and adjust if necessary the Outlet pressure to 1.5
mbar minimum (G20) (or 2.25mbar for G25) (fig.85)
After the adjustment of the low heat, re-verify the high
heat
Re-position the stoppers and close the pressure ports.
After the adjustment of the low heat, re-verify the high
heat
Pressure adjustments table for each type of gas (mbar)
Category
Supply
pressure
Low Heat
Injection mini.
High Heat
Injection
G20 20.0 +/- 1 1.5 +/- 0.03 8.4 +/- 0.2
G25 25.0 +/- 1.3