1 B 2 B 3 B 4 B 5 B 6 B = 2B + 5B 7 B = 3B + 5B 8 B = 4B + 5B
LP1 4,5 6 4,5 6 3,5 4,5 2,5 3,5 4,5 6 4,5 6 3,5 4,5 2,5 3,5
PT1 1,7 2,7 1,7 2,7 1,7 2,7 1,7 2,7 1,7 2,7 1,7 2,7 1,7 2,7 1,7 2,7
LP2 4,5 6 4,5 6 3,5 4,5 2,5 3,5 4,5 6 4,5 6 3,5 4,5 2,5 3,5
PT2 1,7 2,7 1,7 2,7 1,7 2,7 1,7 2,7 1,7 2,7 1,7 2,7 1,7 2,7 1,7 2,7
HP1 43 34 43 34 43 34 43 34 43 34 43 34 43 34 43 34
HP2 43 34 43 34 43 34 43 34 43 34 43 34 43 34 43 34
HPR12 37 30 37 30 37 30 37 30 37 30 37 30 37 30 37 30
PT1/PT2 (*) (*) (*) (*) (*) (*) (*) (*)
HPR22 37 30 37 30 37 30 37 30 37 30 37 30 37 30 37 30
OT1
DT N/A N/A N/A N/A
B2 (*) (*) (*) (*) (*) (*) (*) (*)
15
HEAT PUMP
1.7.- SAFETY DEVICES
1003SM TO 1804SM UNITS
HEATING
EAR
UNIT
STD/FP1/FP2
KIT LOW WATER Tª
0ºC (STD/FP1/FP2)
KIT LOW WATER Tª
-5ºC (STD/FP1/FP2)
KIT LOW WATER Tª
-10ºC (STD/FP1/FP2)
HEATING LOW
AMBIENT KIT -15ºC
(STD/FP1/FP2)
KIT LOW WATER Tª
0ºC HEATING -15ºC
(STD/FP1/FP2)
KIT LOW WATER Tª
-5ºC HEATING -15ºC
(STD/FP1/FP2)
KIT LOW WATER Tª
-10ºC HEATING -15ºC
(STD/FP1/FP2)
cycle set reset cycle set reset cycle set reset cycle set reset cycle set reset cycle set reset cycle set reset cycle set reset
cooling cooling cooling cooling cooling cooling cooling cooling
heating heating heating heating heating heating heating heating
cooling cooling cooling cooling cooling cooling cooling cooling
heating heating heating heating heating heating heating heating
c/h c/h c/h c/h c/h c/h c/h c/h
c/h c/h c/h c/h c/h c/h c/h c/h
cooling cooling cooling cooling cooling cooling cooling cooling
cooling cooling cooling cooling cooling cooling cooling cooling
heating
6ºC differential
2,3
heating
6ºC differential
2,3
heating
6ºC differential
2,3
heating
6ºC differential
2,3
heating
6ºC differential
2,3
heating
6ºC differential
2,3
heating
6ºC differential
2,3
heating
6ºC differential
2,3
heating
118ºC
differential 7
heating
118ºC
differential 7
heating
118ºC
differential 7
heating
118ºC
differential 7
LP / HP / PT / HPR values in Bar. B values in ºC.
(*) CLIMATIC 40 REGULATION
1.-FAN SPEED REGULATION (PT1 y PT2)
EAR STD/FP1/FP2
-Fan start-up 28 Bar
-Cut off 22 Bar
2.-DEFROST CYCLE (PT1 y PT2)
-Start 5,7 Bar
-End 35 Bar
3.-ALARMAS
ANTIFREEZE ALARM (B2)
CUT RESET
STD Unit +3ºC +8ºC
Low water Tª option 0ºC -3ºC -2ºC
Low water Tª option -10ºC -8ºC -7ºC
Low water Tª option -15ºC -13ºC -12ºC
(*) FAN SPEED REGUTATION WITH PROPORTIONAL
CONDENSING PRESSURE CONTROL (FSC/FSC1/FSC2)
(PT1/PT2)
Speed
1.- GENERAL CHARACTERISTICS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox ECOLEAN EAC 1303SM and is the answer not in the manual?

Lennox ECOLEAN EAC 1303SM Specifications

General IconGeneral
BrandLennox
ModelECOLEAN EAC 1303SM
CategoryChiller
LanguageEnglish

Related product manuals