NOTE - For multi-zone systems, the total capacity of all indoor units must be 66% to 133% of the outdoor unit capacity.
Outdoor Unit
Model No.
Number
of
Zones
Indoor Unit
Capacity
Nominal Cooling Capacity at Rated System
Capacity (Btuh)
Nominal Heating Capacity at Rated System
Capacity (Btuh)
#1 #2 #3 #4 #5 #1 #2 #3 #4 #5 #1 #2 #3 #4 #5
MPB048S4M
4
009 009 009 009 - - - 9,250 9,250 9,250 9,250 - - - 9,500 9,500 9,500 9,500 - - -
009 009 009 012 - - - 9,000 9,000 9,000 12,000 - - - 9,500 9,500 9,500 12,500 - - -
009 009 009 018 - - - 9,000 9,000 9,000 17,000 - - - 9,500 9,500 9,500 17,500 - - -
009 009 009 024 - - - 8,500 8,500 8,500 20,500 - - - 9,000 9,000 9,000 21,000 - - -
009 009 012 012 - - - 9,000 9,000 12,000 12,000 - - - 9,500 9,500 13,000 13,000 - - -
009 009 012 018 - - - 9,000 9,000 11,000 17,000 - - - 9,500 9,500 11,500 17,500 - - -
009 009 012 024 - - - 8,500 8,500 10,500 20,500 - - - 9,000 9,000 11,100 21,000 - - -
009 009 018 018 - - - 8,500 8,500 15,500 15,500 - - - 9,000 9,000 16,000 16,000 - - -
009 009 018 024 - - - 8,000 8,000 14,500 20,000 - - - 8,500 8,500 15,000 20,000 - - -
009 012 012 012 - - - 9,000 12,000 12,000 12,000 - - - 9,500 12,500 12,500 12,500 - - -
009 012 012 018 - - - 9,000 11,000 11,000 16,000 - - - 9,500 11,500 11,500 16,500 - - -
009 012 012 024 - - - 8,500 10,000 10,000 20,000 - - - 9,000 10,500 10,500 20,500 - - -
009 012 018 018 - - - 8,500 10,000 15,000 15,000 - - - 9,000 10,500 15,500 15,500 - - -
009 018 018 018 - - - 8,000 14,000 14,000 14,000 - - - 8,500 14,500 14,500 14,500 - - -
012 012 012 012 - - - 12,000 12,000 12,000 12,000 - - - 12,500 12,500 12,500 12,500 - - -
012 012 012 018 - - - 11,000 11,000 11,000 16,000 - - - 11,500 11,500 11,500 16,500 - - -
012 012 012 024 - - - 10,000 10,000 10,000 20,000 - - - 10,500 10,500 10,500 20,500 - - -
012 012 018 018 - - - 10,000 10,000 15,000 15,000 - - - 10,500 10,500 15,500 15,500 - - -
5
009 009 009 009 009 9,000 9,000 9,000 9,000 9,000 9,500 9,500 9,500 9,500 9,500
009 009 009 009 012 9,000 9,000 9,000 9,000 12,000 9,500 9,500 9,500 9,500 13,000
009 009 009 009 018 8,500 8,500 8,500 8,500 16,000 9,000 9,000 9,000 9,000 16,500
009 009 009 009 024 7,750 7,750 7,750 7,750 19,500 8,000 8,000 8,000 8,000 20,000
009 009 009 012 012 9,000 9,000 9,000 11,500 11,500 9,500 9,500 9,500 12,000 12,000
009 009 009 012 018 8,000 8,000 8,000 11,000 16,000 8,500 8,500 8,500 11,500 16,500
009 009 009 018 018 8,000
8,000 8,000 11,000 16,000 8,500 8,500 8,500 16,500 16,500
009 009 012 012 012 8,500 8,500 11,000 11,000 11,000 9,000 9,000 12,000 12,000 12,000
009 009 012 012 018 8,500 8,500 10,000 10,000 15,000 8,500 8,500 10,500 10,500 15,500
009 012 012 012 012 8,000 11,000 11,000 11,000 11,000 8,500 11,500 11,500 11,500 11,500
009 012 012 012 018 7,500 10,000 10,000 10,000 14,500 8,000 10,500 10,500 10,500 15,000
012 012 012 012 012 10,500 10,500 10,500 10,500 10,500 11,000 11,000 11,000 11,000 11,000
1
Oneoutdoorunitmaybematchedwithoneindoorunitforsinglezoneapplications.Asecondindoorunitcanbeaddedatalaterdateformulti-zoneapplications.

Table of Contents

Other manuals for Lennox MMDA048S4-*P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MMDA048S4-*P and is the answer not in the manual?

Lennox MMDA048S4-*P Specifications

General IconGeneral
BrandLennox
ModelMMDA048S4-*P
CategoryAir Conditioner
LanguageEnglish

Related product manuals