MS8C / MS8H (208-230V)
Continued — 18 - 24 kBtu System Status or Error Codes — Indoor Character Display and Outdoor LEDs
Indoor
Unit
Display
Outdoor Unit LED Status
Error Description System Status
Troubleshooting for Possible
Causes
This unit has three display
status indicators
o OFF
n ON ® BLINKS
D5 D6 D16 D30
H3 o
® ®
o
Compressor overload
protection sensor malfunction
All system functions are termi
nated except indoor fan.
Check for proper wiring and loose
connections at outdoor control in
put plug. Also, check for continuity
across overload protection sensor
terminals mounted at top of com
pressor.
H4
n
o
n n
System operating abnormally
All system functions are termi
nated except indoor fan.
See unit information manual.
H5 o
®
o
n
Intelligent Power Module
protection
Intelligent Power Module
protection error can result from
any of the following:
S Loss of cooling to the heat sink
S Low voltage
S High ambient temperature
S Loose screws fastening the
outdoor control to the heat sink
Check all and correct, if necessary.
Lc o
®
o
®
Unit start-up failure
All system functions are termi
nated.
See unit start-up troubleshooting
charts.
L3
n
o o o Fan module protection
Outdoor unit operations are termi
nated. Indoor fan will run.
Check wire connections to outdoor
fan motor or fan motor module on
main board is damaged. Replace
main board.
PH o
n
o
®
High voltage protection
All system functions are termi
nated.
S Check input voltage on outdoor
unit terminal strip (N and L
terminals).
S If voltage is higher than 265VAC,
disconnect power to unit. Correct
input voltage problem before
reapplying power to system.
S If voltage is within normal range,
test capacitor output. If capacitor
range is between 200-208VAC,
replace outdoor control.
PL o
n n
o Low voltage protection
All system functions are termi
nated.
S Check input voltage on outdoor
unit terminal strip (N and L termi
nals).
S If voltage is lower than 150VAC,
restart system and check power
again.
S Check reactor (choke) line con
nection on outdoor control termi
nal marked INDC1.
PU o
n
o
n
Capacitor charge failure
See unit information manual for
further information.
P5 o
®
o o
Compressor overcurrent
protection
P7 o o
n ®
Outdoor control failure Replace outdoor control.
P8
n
o
® n
Intelligent Power Module
temperature is too high
All system functions are termi
nated except indoor fan.
Intelligent Power Module high
temperature error can result from
any of the following:
S Loss of cooling to the heat sink
S Low voltage
S High ambient temperature
S Loose screws fastening the
outdoor control to the heat sink
Check all and correct, if necessary.
U1 o
® n
o
Compressor current test circuit
malfunction
All system functions are termi
nated except indoor fan.
Replace outdoor control.
U3 o
n n n
Unstable DC voltage protection Input voltage is not stable.