XC14 - 1.5 to 5 Ton Air Conditioner / Page 7
SPECIFICATIONS
General
Data
Model No. XC14-041 XC14-042 XC14-047 XC14-048 XC14-060
Nominal Tonnage 3.5 3.5 4 4 5
Connections
(sweat)
Liquid line (o.d.) - in. 3/8 3/8 3/8 3/8 3/8
Suction line (o.d.) - in. 7/8 7/8 7/8 7/8 1-1/8
Refrigerant
1
R-410A charge furnished 10 lbs. 1 oz. 8 lbs. 10 oz. 11 lbs. 3 oz. 10 lbs. 0 oz. 12 lbs. 0 oz.
Outdoor
Coil
Net face area - sq. ft. Outer coil 21 16.33 22 21.00 22.00
Inner coil 20.25 15.71 21.33 20.25 21.33
Tube diameter - in. 5/16 5/16 5/16 5/16 5/16
No. of rows 2 2 2 2 2
Fins per inch 22 22 22 22 22
Outdoor
Fan
Diameter - in. 22 22 26 22 26
No. of blades 4 4 4 4 4
Motor hp 1/4 1/4 1/3 1/4 1/3
Cfm 3600 3500 4400 3600 4400
Rpm 825 825 825 825 825
Watts 310 310 310 310 310
Shipping Data - lbs. 1 pkg. 253 243 284 272 290
ELECTRICAL DATA
Line voltage data - 60hz 208/230V 208/230V-1ph 208/230V 208/230V-1ph 208/230V-1ph
2
Maximum overcurrent protection (amps) 35 40 45 50 60
3
Minimum circuit ampacity 22.8 24.1 26.7 29.0 34.8
Compressor Rated load amps 16.7 17.9 19.9 21.8 26.4
Locked rotor amps 79 112 109 117 134
Power factor 0.97 0.94 0.97 0.95 0.98
Outdoor Fan
Motor
Full load amps 1.7 1.7 1.8 1.7 1.8
Locked rotor amps 3.1 3.1 2.9 3.1 2.9
OPTIONAL ACCESSORIES - MUST BE ORDERED EXTRA
Compressor Hard Start Kit 88M91
Compressor Low Ambient Cut-Off 45F08
Compressor Time-Off Control 47J27
Freezestat 3/8 in. tubing 93G35
5/8 in. tubing 50A93
Low Ambient Kit 34M72
Refrigerant
Line Sets
L15-65-40 L15-65-40
L15-65-50
Field Fabricate
Indoor Blower Off Delay Relay 58M81
NOTE - Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Refrigerant charge sufcient for 15 ft. length of refrigerant lines.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.