EasyManuals Logo

Lenze i510 Series Commissioning

Lenze i510 Series
487 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #288 background imageLoading...
Page #288 background image
11.8.2 Favorites parameter list (default seng)
In the default seng, the most common parameters for the soluon of typical applicaons
are dened as "Favorites":
No. Display code Designaon Default seng Seng range Info
1 P100.00 Output frequency x.x Hz - (Read only) 0x2DDD (P100.00)
2 P103.00 Current actual x.x % - (Read only) 0x6078 (P103.00)
3 P106.00 Motor voltage x VAC - (Read only) 0x2D89 (P106.00)
4 P150.00 Error code - - (Read only) 0x603F (P150.00)
5 P200.00 Control select. Flexible I/O [0] Selecon list 0x2824 (P200.00)
6 P201.01 Freq. setp. src. Analog input 1 [2] Selecon list 0x2860:001 (P201.01)
7 P203.01 Start method Normal [0] Selecon list 0x2838:001 (P203.01)
8 P203.03 Stop method Standard ramp [1] Selecon list 0x2838:003 (P203.03)
9 P208.01 Mains voltage 230 Ve [0] Selecon list 0x2540:001 (P208.01)
10 P210.00 Min. frequency 0.0 Hz 0.0 ... 599.0 Hz 0x2915 (P210.00)
11 P211.00 Max. frequency 50.0 Hz* | 60.0 Hz** 0.0 ... 599.0 Hz 0x2916 (P211.00)
12 P220.00 Accelerat.me 1 5.0 s 0.0 ... 3600.0 s 0x2917 (P220.00)
13 P221.00 Decelerat.me 1 5.0 s 0.0 ... 3600.0 s 0x2918 (P221.00)
14 P300.00 Motor ctrl mode VFC open loop [6] Selecon list 0x2C00 (P300.00)
15 P302.00 V/f charac.shape Linear [0] Selecon list 0x2B00 (P302.00)
16 P303.01 Base voltage 230 V 0 ... 5000 V 0x2B01:001 (P303.01)
17 P303.02 Base frequency 50 Hz* | 60 Hz** 0 ... 1500 Hz 0x2B01:002 (P303.02)
18 P304.00 Limit. rotaon Both rot. direct [1] Selecon list 0x283A (P304.00)
19 P305.00 Switching freq. 0 Selecon list 0x2939 (P305.00)
20 P308.01 Max.load.for 60s 150 % 30 ... 200 % 0x2D4B:001 (P308.01)
21 P316.01 Fixed V/f boost 2.5 % 0.0 ... 20.0 % 0x2B12:001 (P316.01)
22 P323.00 Motor current 1.700 A 0.001 ... 500.000 A 0x6075 (P323.00)
23 P324.00 Max current 200.0 % 0.0 ... 3000.0 % 0x6073 (P324.00)
24 P400.01 Enable inverter TRUE [1] Selecon list 0x2631:001 (P400.01)
25 P400.02 Run Digital input 1 [11] Selecon list 0x2631:002 (P400.02)
26 P400.03 Quick stop Not connected [0] Selecon list 0x2631:003 (P400.03)
27 P400.04 Reset fault Digital input 2 [12] Selecon list 0x2631:004 (P400.04)
28 P400.05 DC braking Not connected [0] Selecon list 0x2631:005 (P400.05)
29 P400.06 Start forward Not connected [0] Selecon list 0x2631:006 (P400.06)
30 P400.07 Start reverse Not connected [0] Selecon list 0x2631:007 (P400.07)
31 P400.08 Run forward Not connected [0] Selecon list 0x2631:008 (P400.08)
32 P400.09 Run reverse Not connected [0] Selecon list 0x2631:009 (P400.09)
33 P400.13 Reverse rot.dir. Digital input 3 [13] Selecon list 0x2631:013 (P400.13)
34 P400.18 Setp: Preset b0 Digital input 4 [14] Selecon list 0x2631:018 (P400.18)
35 P400.19 Setp: Preset b1 Digital input 5 [15] Selecon list 0x2631:019 (P400.19)
36 P400.20 Setp: Preset b2 Not connected [0] Selecon list 0x2631:020 (P400.20)
37 P420.01 Relay funcon Rdy for operat. [51] Selecon list 0x2634:001 (P420.01)
38 P420.02 DO1 funcon Release brake [115] Selecon list 0x2634:002 (P420.02)
39 P430.01 AI1 input range 0 ... 10 VDC [0] Selecon list 0x2636:001 (P430.01)
40 P430.02 AI1 freq @ min 0.0 Hz -1000.0 ... 1000.0 Hz 0x2636:002 (P430.02)
41 P430.03 AI1 freq @ max 50.0 Hz* | 60.0 Hz** -1000.0 ... 1000.0 Hz 0x2636:003 (P430.03)
42 P440.01 AO1 outp. range 0 ... 10 VDC [1] Selecon list 0x2639:001 (P440.01)
43 P440.02 AO1 funcon Outp. frequency [1] Selecon list 0x2639:002 (P440.02)
44 P440.03 AO1 min. signal 0 -2147483648 ... 2147483647 0x2639:003 (P440.03)
45 P440.04 AO1 max. signal 1000 -2147483648 ... 2147483647 0x2639:004 (P440.04)
46 P450.01 Freq. preset 1 20.0 Hz 0.0 ... 599.0 Hz 0x2911:001 (P450.01)
47 P450.02 Freq. preset 2 40.0 Hz 0.0 ... 599.0 Hz 0x2911:002 (P450.02)
48 P450.03 Freq. preset 3 50.0 Hz* | 60.0 Hz** 0.0 ... 599.0 Hz 0x2911:003 (P450.03)
49 P450.04 Freq. preset 4 0.0 Hz 0.0 ... 599.0 Hz 0x2911:004 (P450.04)
50 - - - - not assigned
* Device for 50-Hz mains ** Device for 60-Hz mains Firmware version 05.00.00.00
Addional funcons
Favorites
Favorites parameter list (default seng)
288

Table of Contents

Other manuals for Lenze i510 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i510 Series and is the answer not in the manual?

Lenze i510 Series Specifications

General IconGeneral
Protection ClassIP20
Overload Capacity150% for 60 seconds
Enclosure RatingIP20
DimensionsVaries by model
WeightVaries by model
Control TypeV/f control, vector control
Communication InterfacesCANopen, Modbus RTU, EtherCAT, PROFIBUS, PROFINET
Ambient Temperature-10°C to +50°C
Braking ResistorOptional
SafetySTO (Safe Torque Off)
Protection FeaturesOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Output Voltage0 to input voltage
Input Voltage200-240 V, 380-480 V
Voltage Range200-240 V, 380-480 V
Frequency Range0 to 599 Hz