14.15.3 Digital output 2
Sengs for digital output 2.
Precondions
Control Unit (CU) with applicaon I/O
Details
The digital output 2 is controlled with the trigger selected in 0x2634:003 (P420.03).
The following sengs are possible for the digital output:
•
Inversion
①
•
Switch-on delay
②
•
Cutout delay
③
DO2
0x4017:0050x4017:006
1
0
1
0x2635 003: 0x4017 004: 0x4017:003
0x2634:003
X3
Trigger
Diagnosc parameters:
•
The logic status of the trigger signal is displayed in 0x4017:006.
•
The logic status of the digital output is displayed in 0x4017:005.
Parameter Name / value range / [default seng] Info
0x2634:003
(P420.03)
Digital outputs funcon: Digital output 2
(Dig.out.funcon: DO2 funcon)
•
Only available for applicaon I/O.
•
For further possible sengs, see parameter
0x2634:001 (P420.01). ^ 603
Assignment of a trigger to digital output 2.
Trigger = FALSE: X3/DO2 set to LOW level.
Trigger = TRUE: X3/DO2 set to HIGH level.
Notes:
•
An inversion set in 0x2635:003 (P421.03) is taken into consideraon
here.
56 Error acve
100 Sequencer controlled (from version 03.00) The control is executed via the sequencer (according to the congura-
on of the digital outputs for the current segment).
4Segment conguraon ^ 506
0x2635:003
(P421.03)
Inversion of digital outputs: Digital output 2
(DO inversion: DO2 inversion)
•
Only available for applicaon I/O.
Inversion of digital output 2
0 Not inverted
1 Inverted
0x4017:003 Digital output 2: Cutout delay
0.000 ... [0.000] ... 65.535 s
•
Only available for applicaon I/O.
Switch-o delay for digital output 2.
Note!
The set delay me is not eecve (internally set to "0") if the relay is
assigned to the trigger "Release holding brake [115]". Only the decelera-
on me set in 0x2820:012 (P712.12)for closing the holding brake inu-
ences the me-dependent behaviour of the digital output.
0x4017:004 Digital output 2: Switch-on delay
0.000 ... [0.000] ... 65.535 s
•
Only available for applicaon I/O.
Switch-on delay for digital output 2.
Note!
The set delay me is not eecve (internally set to "0") if the relay is
assigned to the trigger "Release holding brake [115]". Only the decelera-
on me set in 0x2820:012 (P712.12)for closing the holding brake inu-
ences the me-dependent behaviour of the digital output.
0x4017:005 Digital output 2: Terminal state
•
Read only
•
Only available for applicaon I/O.
Display of the logic state of output terminal X3/DO2.
0 FALSE
1 TRUE
0x4017:006 Digital output 2: Trigger signal state
•
Read only
•
Only available for applicaon I/O.
Display of the logic state of the trigger signal for digital output 2 (without
taking a ON/OFF delay set and inversion into consideraon).
0 FALSE
1 TRUE
Flexible I/O conguraon
Conguraon of digital outputs
Digital output 2
608