25505 0x63A1 CU: load error ID tag Keypad display: CU ID tag error
Cause Error type/response Remedy
Calibraon data of the control unit not compa-
ble or faulty.
Fault
The inverter is inhibited immediately. The
motor becomes torqueless (coasts).
The error can only be reset by mains switch-
ing.
Update rmware of the inverter to the most
recent version.
If the error persists, the control unit or the
device has to be replaced. In this case, please
contact the manufacturer.
25506 0x63A2 PU: load error ID tag Keypad display: PU ID tag error
Cause Error type/response Remedy
Calibraon data of the power unit not compa-
ble or faulty.
Fault
The inverter is inhibited immediately. The
motor becomes torqueless (coasts).
The error can only be reset by mains switch-
ing.
Update rmware of the inverter to the most
recent version.
If the error persists, the power unit or the
device has to be replaced. In this case, please
contact the manufacturer.
25507 0x63A3 Power secon unknown Keypad display: PU unknown
Cause Error type/response Remedy
The power unit installed is not supported by the
soware.
Fault
The inverter is inhibited immediately. The
motor becomes torqueless (coasts).
The error can only be reset by mains switch-
ing.
Update rmware of the inverter to the most
recent version.
28800 0x7080 Monitoring of connecon level (Low/High) Keypad display: Asseronlevel
Cause Error type/response Remedy
The last seng of the connecon level diers
from the saved seng.
Fault
1.
Check seng in 0x2630:001 (P410.01).
2.
Execute device command "Save user data"
0x2022:003 (P700.03).
3.
Switch inverter o and on again.
28801 0x7081 Error of analog input 1 Keypad display: AI1 fault
Cause Error type/response Remedy
The monitoring funcon of the input signal con-
gured for analog input 1 in 0x2636:008
(P430.08) and 0x2636:009 (P430.09) has been
triggered.
Fault
The error type can be congured in
0x2636:010 (P430.10).
Check input signal at analog input 1.
Check conguraon of the monitoring func-
on.
Related topics
4Analog input 1 ^ 597
28802 0x7082 Error of analog input 2 Keypad display: AI2 fault
Cause Error type/response Remedy
The monitoring funcon of the input signal con-
gured for analog input 2 in 0x2637:008
(P431.08) and 0x2637:009 (P431.09) has been
triggered.
Fault
The error type can be congured in
0x2637:010 (P431.10).
Check input signal at analog input 2.
Check conguraon of the monitoring func-
on.
Related topics
4Analog input 2 ^ 601
Appendix
Error codes