Application Note #461
3 Technical Support — 800.523.9466
Sensor Mode
• Auto-On Daylight Sensing is the mode in which the light turns on only if natural light in the room is low. If the switch
turns on when there is enough natural light, or if the switch does not turn on when there is not enough natural light,
press the On/Off button within 5 seconds of entering the room. Over time, this interaction will “teach” the switch your
preferred setting.
• Manual Off-While-Occupied is a feature that can be enabled or disabled to accommodate different lighting scenarios.
Enabled: When the occupancy sensing switch is manually turned off, the light will turn off and remain off while the
room is occupied (e.g., during the viewing of a presentation in a conference room or classroom).
Disabled: When the occupancy sensing switch is manually turned off, the light will turn off. After 25 seconds have
elapsed, the light will turn on and remain on for as long as the occupancy sensor detects motion in the room.
Manual Off-While-Occupied Actions
Sequence of Events Enabled Disabled
Room is occupied Light is ON Light is ON
Occupancy sensing switch is manually turned off Light turns OFF Light turns OFF
Room remains occupied Light remains OFF Light turns ON after 25seconds
Room is vacated Light remains OFF Light remains OFF
Timeout period expires Light remains OFF Light turns OFF
Room becomes occupied Light turns ON Light turns ON
Model Numbers
MS-OPS6M2-DV
MS-OPS6M2N-DV
Number
of flashes
1
Auto-On and Auto-Off (Occupancy mode);
Off-while-occupied ENABLED
2 Manual-On and Auto-Off (Vacancy mode)
3
Auto-On daylight sensing and Auto-Off;
Off-while-occupied ENABLED
4
Auto-On and Auto-Off (Occupancy mode);
Off-while-occupied DISABLED
Model Numbers
MS-OPS2
MS-OPS5M
Number
of flashes
1
Auto-On and Auto-Off (Occupancy mode);
Off-while-occupied DISABLED
2 Manual-On and Auto-Off (Vacancy mode)
3
Auto-On daylight sensing and Auto-Off;
Off-while-occupied ENABLED
4
Auto-On and Auto-Off (Occupancy mode);
Off-while-occupied ENABLED
Example 2: Changing the Sensor Mode to Auto-On Daylight Sensing and Manual Off-While-Occupied enabled.
1. Press and hold the Auxiliary button.
2. Release the button after the lens flashes for the third time.

Other manuals for Lutron Electronics MAESTRO MS-OPS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lutron Electronics MAESTRO MS-OPS2 and is the answer not in the manual?

Lutron Electronics MAESTRO MS-OPS2 Specifications

General IconGeneral
BrandLutron Electronics
ModelMAESTRO MS-OPS2
CategorySwitch
LanguageEnglish

Related product manuals