200 Part Number STH025 11/16
Harvest Cycle
REMOTE CONDENSER
The head pressure control cycles into full bypass due
to the pressure drop when the harvest valve opens.
Refrigerant flows from the compressor to the evaporator
through the harvest valve and the head pressure valve is
out of the circuit.
Undercharge Symptoms
• Safety limit #1 or Safety limit #2 in control board
memory, a flashing triangle alert and after pressing
left arrow Long Freeze or Long Harvest is displayed.
• Harvest cycle suction pressure is low.
• Harvest cycle discharge pressure is low.
• Liquid line entering receiver feels warm to hot in the
freeze cycle.
Overcharge Symptoms
• Safety limit #2 in control board memory, a flashing
triangle alert and after pressing left arrow Long
Harvest is displayed.
• Harvest cycle discharge pressure is normal.
• Freeze cycle time, suction and discharge pressure
are normal and the ice machine will not harvest. The
sheet of ice cubes show little or no sign of melting
when removed from the evaporator after the harvest
cycle has been completed. (If the cubes are melted
you have a release problem, clean the ice machine).