Section 7 Refrigeration System
Part No. 80-1100-3 7-15
Safety Limit #1
Refer to page 7-13 for control board identification and safety limit operation.
Control Board with Black Microprocessor - Freeze Time exceeds 60 minutes for 3 consecutive freeze cycles
or
Control Board with Orange Label on Microprocessor - Freeze time exceeds 60 minutes for 6 consecutive freeze
cycles.
SAFETY LIMIT NOTES
Because there are many possible external problems,
do not limit your diagnosis to only the items listed in
this chart.
A continuous run of 100 harvests automatically
erases the safety limit code.
The control board will store and indicate only one
safety limit – the last one exceeded.
If the toggle switch is moved to the OFF position and
then back to the ICE position prior to reaching the
100-harvest point, the last safety limit exceeded will
be indicated.
If the harvest light did not flash prior to the ice
machine restarting, then the ice machine did not stop
because it exceeded a safety limit.
Possible Cause Check/Correct
Improper installation See “Installation/Visual Inspection Checklist” on Page 7-10
Water system Low water pressure (20 psi min.)
High water pressure (80 psi max.)
High water temperature (90°F/32.2°C max.)
Clogged water distribution tube
Dirty/defective water fill valve
Dirty/defective water dump valve
Defective water pump
Electrical system Ice thickness probe out of adjustment
Harvest cycle not initiated electrically
Contactor not energizing
Compressor electrically non-operational
Restricted condenser
air flow (air-cooled models)
High inlet air temperature (110°F/43.3°C max.)
Condenser discharge air recirculation
Dirty condenser filter
Dirty condenser fins
Defective fan cycling control
Defective fan motor
Restricted condenser water flow (water-cooled models) Low water pressure (20 psi min.)
High water temperature (90°F/32.2°C max.)
Dirty condenser
Dirty/defective water regulating valve
Water regulating valve out of adjustment
Refrigeration system Non-Manitowoc components
Improper refrigerant charge
Defective head pressure control (remotes)
Defective harvest valve
Defective compressor
TXV starving or flooding (check bulb mounting)
Non-condensables in refrigeration system
Plugged or restricted high side refrigerant lines or component

Table of Contents

Other manuals for Manitowoc QY0375W

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc QY0375W and is the answer not in the manual?

Manitowoc QY0375W Specifications

General IconGeneral
BrandManitowoc
ModelQY0375W
CategoryIce Maker
LanguageEnglish

Related product manuals