• Remove burr with the burr remover. Hold the flaring end down to prevent burrs from dropping inside pipe.
• The exact length of pipe protruding from the face of the flare die is determined by the flaring tool. The table shows the
use of an imperial die and riged die.
IMPERIAL DIE RIGED DIE
6.35 (1/4”) 1.3 0.7
9.52 (3/8”) 1.6 1
12.7 (1/2”) 1.9 1.3
15.88 (5/8”) 2.2 1.7
A(mm)
PIPE ∅, D (mm)
Fix the pipe firmly on the flare die. Match the centers of both the flare die and the flaring punch, and tighten
flaring punch fully.
84
8) Vacuuming And Charging
• The precharged outdoor unit does not need any vacuuming or charging. However once it is connected, the
connecting pipe line and the indoor need to be vacuumed before releasing the R22/R407C/R410A from
the outdoor unit.
1) Open the service port core cap.
2) Connect pressure gauge to the service port.
3) Connect the line to vacuum pump. Open the charging manifold valve and turn the pump on. Vacuum to
–0.1 MPa (-760mmHg) or lower. (Evacuation time varies by the pump but averagely in 1 hour).
Note : R407C – Fix filter dryer
R22 - Nil
R410A - Nil
4) After evacuation, unscrew the spindle (diagram B) for the gas to run to indoor unit.