8
Cooling only
NOTES :
1. ALL UNITS ARE BEING TESTED AND COMPLY TO ARI210/240-94.
2. NOMINAL COOLING CAPACITIES ARE BASED ON THE FOLLOWING CONDITIONS. INDOOR 26.7 °CDB, 19.4 °CWB, OUTDOOR 35 °CDB.
3. ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY MANUFACTURER WITHOUT PRIOR NOTICE.
4. AIR FILTER IS AN OPTIONAL ITEM.
MODEL INDOOR UNIT
MDB150B1 MDB150C1
OUTDOOR UNIT
MMC100B x 2
MMC100C x 2
TOTAL OUTDOOR Btu/h
150,000 150,000
COOLING
35 °CDB
kcal/h
37,800
37,800
CAPACITY W
43,950 43,950
MATERIAL
CASING FINISHING
INSULATION
HEIGHT (H)
mm (in)
885 (34.84)
736 (28.97)
DIMENSION WIDTH (W) mm (in)
1,640 (64.56) 1,819 (71.61)
DEPTH (D)
mm (in)
1,040 (40.94)
965 (37.99)
NET WEIGHT
kg (lb)
145 (319)
188 (414)
NOISE LEVEL (SOUND POWER) dBA
79 79
EVAPORATOR COIL
TYPE
MATERIAL
TUBE
WALL THICKNESS
mm (in)
OUTER DIAMETER mm (in)
MATERIAL
FIN THICKNESS mm (in)
ROWS
4 4
FIN PER INCH
12
14
CAPACITY STEP %
100-50-0 100-50-0
FACE AREA
m
2
(ft
2
)
1.00 (10.82)
0.90 (9.80)
FACE VELOCITY m/min (FPM)
129.54 (425)
142.94 (469)
EVAPORATOR BLOWER
TYPE / DRIVE
BLOWER MATERIAL
BLOWER DIAMETER
mm (in)
394.97 (15.55)
394.97 (15.55)
BLOWER LENGTH mm (in)
381.00 (15.00) 381.00 (15.00)
AIR FLOW
CMM (CFM)
130.31(4,600)
130.31 (4,600)
EXTERNAL STATIC PRESSURE mm wg (in wg)
15.24 (0.60)
15.24 (0.60)
BLOWER PULLEY DIAMETER mm
1 SPZ 160 2 SPZ 125
MOTOR PULLEY DIAMETER mm
1 SPZ 80
2 SPZ 71
PULLEY TYPE
B1 B1
EVAPORATOR BLOWER MOTOR
TYPE
POWER SUPPLY V / Ph / Hz
NUMBER x RATED RUNNING CURRENT
A
3.39
4.65
NUMBER x RATED OUTPUT W
1,500 2,200
NUMBER x RATED INPUT
W
1,630
1,682
MOTOR POLES
4
4
REFRIGERANT
TYPE
TYPE OF GAS PRECHARGED
CONTROL
PIPE CONNECTION
PIPE SIZE LIQUID mm (in)
15.88 (5/8) 15.88 (5/8)
GAS
mm (in)
34.92 (1-3/8)
34.92 (1-3/8)
DRAIN PIPE CONNECTION mm (in)
AIR FILTER
TYPE
SIZE LENGTH x HEIGHT mm
457 x 738 516.5 x 589
DEPTH
mm (in)
50.8 (2.00)
50.8 (2.00)
QUANTITY
3 3
INDOOR UNIT
MDB200B2 MDB250B2
MMC150C
MMC125B x 2
200,000
50,400
58,600
250,000
63,000
ZINC COATED STEEL
181.30 (6,400)
15.24 (0.60)
73,250
1,291 (50.82)
0.35 (0.013)
9.52 (3/8)
ALUMINIUM
0.127 (0.005)
100-50-0
4
12
4
14
542 x 738
50.8 (2.00)
3
533 x 532
50.8 (2.00)
6
WASHABLE VILEDON
ELECTRO GALVANIZED MILD STEEL
EPOXY POLYESTER POWDER COATING
PE
945 (37.20)
100-50-0
1.20 (12.92)
150.87 (495)
1.48 (16.01)
152.40 (500)
1,894 (74.56)
980 (38.58)
180 (396)
SEAMLESS COPPER
1,866 (73.46)
1,199 (47.20)
250 (551)
85 87
CROSS FINNED TUBES
CENTRIFUGAL / BELT DRIVEN
SQUIRREL CAGE INDUCTION
B1
2 SPZ 180
2 SPZ 90
B2
226.62 (8,000)
20.32 (0.80)
2 SPZ 140
2 SPZ 80
BRAZING
NITROGEN HOLDING
25.40 (1.00)
15.88 (5/8)
28.58 (1-1/8)
15.88 (5/8)
31.75 (1 1/4)
THERMOSTAT EXPANSION VALVE
400 / 3 / 50
R22
8.00
4,000
3,370
4
6.15
3,000
2,730
4
394.97 (15.55)
381.00 (15.00)
469.90 (18.50)
459.99 (18.11)
CASING
MATERIAL
FINISHING
HEIGHT (H)
mm (in)
946 (37.24)
971.4 (38.24)
DIMENSION WIDTH (W) mm (in)
1,116 (43.93)
1,393 (54.84)
DEPTH (D) mm (in)
939 (36.96) 500 (19.68)
NET WEIGHT kg (lb)
193 (425)
176 (387)
NOISE LEVEL (SOUND POWER) dBA
72 75
CONDENSER COIL
TYPE
MATERIAL
TUBE WALL THICKNESS mm (in)
OUTER DIAMETER mm (in)
MATERIAL
FIN THICKNESS mm (in)
NUMBER x ROWS
2 x 2
1 x 3
FIN PER INCH
12 14
FACE AREA
m
2
(ft
2
)
1.76 (19.00)
1.35 (14.54)
FACE VELOCITY m/min (FPM)
112.16 (368)
146.60 (481)
CONDENSER FAN
DRIVE
TYPE
P. SPLIT CAPACITOR
INDUCTION
BLADE MATERIAL
BLADE DIAMETER mm (in)
660.40 (26) 762.00 (30)
POWER SUPPLY V / Ph / Hz
380-415/3/50
380-415/3/50
NUMBER x RATED RUNNING CURRENT A
1.50 3.35
NUMBER x RATED INPUT
W
660
1,100
MOTOR POLES
6 8
AIR FLOW
CMM (CFM)
198.30 (7,000)
198.30 (7,000)
COMPRESSOR
TYPE
POWER SUPPLY V / Ph / Hz
RATED RUNNING CURRENT
A
16.9
16.9
RATED INPUT W
9,040
9,040
MAXIMUM STARTING CURRENT A
125.0 125.0
PROTECTION DEVICE
STAGE OF CAPACITY CONTROL
STARTER TYPE
REFRIGERANT
TYPE
TYPE OF GAS PRECHARGED
NITROGEN HOLDING
198.0
AUTO-TRANSFORMER
OUTDOOR UNIT
640
6
198.30 (7,000)
17.9
380-415/3/50
660.40 (26)
R22
10,200
110.0
4.35
3,200
6
OVERLOAD PROTECTION AND AUTO RESET HIGH / LOW PRESSURE SWITCH
ON / OFF
23.5
13,300
PROPELLER / DIRECT
SCROLL
ALUMINIUM
762.00 (30)
380-415 / 3 / 50
328.61 (11,600)
PERMANENT SPLIT CAPACITORINDUCTION
1.43
380-415/3/50
0.35 (0.013)
9.52 (3/8)
ALUMINIUM
0.127 (0.005)
CROSS FINNED TUBES
SEAMLESS COPPER
1,116 (43.93)
939 (36.96)
224 (493)
75
1,116 (43.93)
939 (36.96)
258 (568)
77
1,041 (40.98)
946 (37.24)
ELECTRO GALVANIZED MILD STEEL
EPOXY POLYESTER POWDER
2 x 2
16
1.76 (19.00)
112.16 (368)
2 x 2
14
1.24 (13.38)
131.97 (433)