VC Pro VRF 50/60Hz
135
Part 2 - Outdoor Unit Engineering Data
10 Sound Levels
10.1 Overall
Table 2-10.1: Sound pressure level
Model
dB(A)
Model
dB(A)
Model
dB(A)
8HP
57
36HP
65
64HP
66
10HP
58
38HP
65
66HP
66
12HP
60
40HP
65
68HP
67
14HP
60
42HP
65
70HP
67
16HP
61
44HP
66
72HP
67
18HP
62
46HP
66
74HP
68
20HP
63
48HP
66
76HP
68
22HP
63
50HP
66
78HP
68
24HP
64
52HP
66
80HP
68
26HP
64
54HP
66
82HP
68
28HP
64
56HP
66
84HP
68
30HP
64
58HP
66
86HP
68
32HP
64
60HP
66
88HP
68
34HP
65
62HP
66
90HP
68
Notes:
1. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber. During in-situ operation, sound
pressure levels may be higher as a result of ambient noise.
Figure 2-10.1: Sound pressure level measurement (unit: mm)
1000
1300
Front

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MVC-560WV2GN1 and is the answer not in the manual?

Midea MVC-560WV2GN1 Specifications

General IconGeneral
BrandMidea
ModelMVC-560WV2GN1
CategoryAir Conditioner
LanguageEnglish

Related product manuals