VC Pro VRF 50/60Hz
156
Midea VC Pro Series Engineering Data Book
Table 3-4.5: Main pipe
1
(L
1
) and first indoor branch joint (A)
Total capacity of
outdoor units
Equivalent length of all liquid pipes < 90m
Equivalent length of all liquid pipes 90m
Gas pipe (mm)
Liquid pipe (mm)
Branch joint kit
Gas pipe (mm)
Liquid pipe (mm)
Branch joint kit
8HP
Φ19.1
Φ9.53
FQZHN-02D
Φ22.2
Φ9.53
FQZHN-02D
10HP
Φ22.2
Φ9.53
FQZHN-02D
Φ25.4
Φ9.53
FQZHN-02D
12-14HP
Φ25.4
Φ12.7
FQZHN-02D
Φ28.6
Φ12.7
FQZHN-03D
16HP
Φ28.6
Φ12.7
FQZHN-03D
Φ31.8
Φ12.7
FQZHN-03D
18-24HP
Φ28.6
Φ15.9
FQZHN-03D
Φ31.8
Φ15.9
FQZHN-03D
26-34HP
Φ31.8
Φ19.1
FQZHN-03D
Φ38.1
Φ19.1
FQZHN-04D
36-54HP
Φ38.1
Φ19.1
FQZHN-04D
Φ41.3
Φ19.1
FQZHN-04D
56-66HP
Φ41.3
Φ19.1
FQZHN-05D
Φ44.5
Φ19.1
FQZHN-05D
68-82HP
Φ44.5
Φ22.2
FQZHN-05D
Φ54.0
Φ22.2
FQZHN-06D
84-90HP
Φ50.8
Φ25.4
FQZHN-05D
Φ54.0
Φ25.4
FQZHN-07D
Notes:
1. The main pipe (L
1
) and first indoor branch joint (A) should be sized according to whichever of Tables 3-4.4 and 3-4.5 indicates the larger size.
Figure 3-4.4: Outdoor connection pipes
Two units combination
Three units combination
Table 3-4.6: Outdoor connection pipes (g1 to g3, G
1
)
Table 3-4.7: Outdoor branch joint kits (L to M)
Pipes
Outdoor unit
capacity
Gas pipe (mm)
Liquid pipe (mm)
No. of outdoor
units
Branch joint kit
g1 to g3
8-12HP
Φ25.4
Φ12.7
2
FQZHW-02N1E
14-22HP
Φ31.8
Φ15.9
3
FQZHW-03N1E
24-30HP
Φ38.1
Φ19.1
G
1
Φ41.3
Φ22.2
Table 3-4.8: Indoor auxiliary pipes (a to q)
Capacity of indoor unit
(kW)
Pipe length 10m
Pipe length > 10m
1
Gas pipe (mm)
Liquid pipe (mm)
Gas pipe (mm)
Liquid pipe (mm)
≤ 4.5
Φ12.7
Φ6.35
Φ15.9
Φ9.53
≥ 5.6
Φ15.9
Φ9.53
Φ19.1
Φ12.7
Notes:
1. An indoor auxiliary pipe should not be larger than the indoor main pipe immediately upstream of it. For indoor auxiliary
pipes greater than 10m in length with indoor units of capacity great than or equal to 5.6kW, the gas and liquid side pipes
should each either be sized according to this table, or else be the same size as the indoor main pipe immediately upstream,
whichever is smaller.
Main pipe
S
g1g2
S
R
g1g2
G1
g3
Main pipe