Job Name: Location:
Engineer Name: Contractor:
System No.: Date:
Model: PUHY-P192TSKMU-A
(Consists of One PUHY-P120TKMU-A, One PUHY-P72TKMU-A and One CMY-Y100CBK3 Twinning Kit)
OUTDOOR VRF HEAT PUMP SYSTEM FEATURES
• 3-phase, 208/230V
• Modular variable refrigerant flow (VRF) systems;
smaller capacity units can be piped together to form a single,
large-capacity two-pipe system
• Required Twinning Kit allows for easy field piping connection
• Selectable fan static, 0.12 or 0.24"WG external static pressure;
factory set to 0"WG
• Connects to CITY MULTI indoor units; controlled via
CITY MULTI Controls Network (CMCN)
• External finish: Pre-coated Galvanized-steel Sheets
• Operating Temperature Range
Cooling (Outdoor): 23° ~ 115°F (-5° ~ +46°C) DB
Heating (Outdoor): -4° ~ +60°F (-20° ~ +16°C) WB
OPTIONAL PARTS
□ Twinning Kit*.…………………………………...…….CMY-Y100CBK3
□ T-Branch Joint (≤ 72,000 Btu/h)………………..........CMY-Y102SS-G2
□ T-Branch Joint (≤ 144,000 Btu/h)……………….…....CMY-Y102LS-G2
□ T-Branch Joint (≤ 234,000 Btu/h)……………….........CMY-Y202S-G2
□ Header (4-Branch; ≤ 72,000 Btu/h)........………………CMY-Y104C-G
□ Header (8-Branch; ≤ 144,000 Btu/h)......………………CMY-Y108C-G
□ Header (10-Branch; ≤ 234,000 Btu/h)....………………CMY-Y1010C-G
* Twinning Kit is necessary to combine the refrigerant flows of the
modules and is sold separately.
Specifications System Module 1 Module 2
Unit Type PUHY-P192TSKMU-A PUHY-P120TKMU-A PUHY-P72TKMU-A
Nominal Cooling Capacity Btu/h 192,000 120,000 72,000
Nominal Heating Capacity Btu/h 215,000 135,000 80,000
External Dimensions (H x W x D) In. / mm Refer to Module Data
65 x 68-29/32 x 29-5/23 /
1,650 x 1,750 x 740
65 x 36-1/4 x 29-5/32 /
1,650 x 920 x 740
Net Weight Lbs. / kg 1,127 / 511 697 / 316 430 / 195
Electrical Power Requirements Voltage, Phase, Hertz Refer to Module Data** 208 / 230V, 3-phase, 60Hz**
Cooling Power Input kW 14.81
Refer to System Data
Heating Power Input kW 16.91
Cooling Current (208/230V) R.L.A. 45.6 / 41.3
Refer to System Data
Heating Current (208/230V) R.L.A. 52.1 / 47.1
Minimum Circuit Ampacity
(MCA)**
A Refer to Module Data** 45 / 42** 25 / 23**
Maximum Breaker Size**
A Refer to Module Data** 50** 30**
Maximum Overcurrent Protection** A Refer to Module Data** 73 / 67** 42 / 38**
Piping Diameter
Refer to System Data
From Twinning Kit to Indoor Units
(Brazed) (In. / mm)
Liquid (High Pressure) 5/8 / 15.88
Gas (Low Pressure) 1-1/8 / 28.58
From Modules to Twinning Kit
(Brazed) (In. / mm)
Liquid (High Pressure)
Refer to Module Data
1/2 / 12.7 3/8 / 9.52
Gas (Low Pressure) 1-1/8 / 28.58 7/8 x 22.2
Indoor Unit
Total Capacity 50 to 130% of ODUs
Refer to System Data
Model / Quantity P06 ~ P96 / 2 to 41
Sound Pressure Levels dB(A) 62.5 60.0 58.0
Fan
Refer to Module Data
Type x Quantity Propeller Fan x 2 Propeller Fan x 1
Airflow Rate CFM 11,300 6,200
Direct-drive Inverter Motor Output kW 0.92 + 0.92 0.92
Compressor Operating Range 6% to 100% Refer to System Data
Compressor Type x Quantity
Refer to Module Data
Inverter-driven Scroll Hermetic x 1 Inverter-driven Scroll Hermetic x 1
Compressor Motor Output kW 8.1 5.5
Compressor Crankcase Heater kW - -
Refrigerant
Refer to Module Data
R410A
Lubricant MEL32
High-pressure Protection Device
Refer to Module Data
601 psi / 4.15 MPa 601 psi / 4.15 MPa
Compressor / Fan Protection Device Overheat Protection / Thermal Switch Overheat Protection / Thermal
Switch
Inverter Protection Device Overheat / Overcurrent Protection Overheat / Overcurrent Protection
Blue Fin Anti-corrosion Protection: Cellulose- and polyurethane-resin coating treatment applied to condenser coil that protects it from air contaminants;
≥1μm thick; Salt Spray Test Method - no unusual rus
t development to 480 hours.
PUHY-P120TKMU-A
** Each individual module requires a separate electrical connection. Reference electrical data for each individual module.
PUHY-P72TKMU-A