Job Name: Location: Date:
Purchaser: Engineer:
Submitted to: For Reference Approval Construction
Unit Designation: Schedule No.:
Cooling*
Rated Capacity...............................35,000 Btu/h
Minimum Capacity ............................12,000 Btu/h
SEER ..................................... 15.0 Btu/h/W
EER ....................................... 7.2 Btu/h/W
Total Input .....................................4,850 W
* Rating Conditions (Cooling) - Indoor: 80ºF (27ºC) DB / 67ºF (19ºC) WB.
Outdoor: 95ºF (35ºC) DB / 75ºF (24ºC) WB.
Electrical Requirements
Power Supply ....................208 / 230V, 1-Phase, 60 Hz
Recommended Fuse/Breaker Size.......................30 A
Voltage
Indoor - Outdoor S1-S2 ......................AC 208 / 230V
Indoor - Outdoor S2-S3 ............................DC24V
Indoor - Remote Controller..........................DC12V
OPERATING CONDITIONS
Indoor Intake Air Temp. Outdoor Intake Air Temp.
Cooling
Maximum 95ºF (35ºC) DB, 71ºF (22ºC) WB 115ºF (46ºC) DB
Minimum 67ºF (19ºC) DB, 57ºF (14ºC) WB 0ºF** (-18ºC) DB
** With optional wind bafe accessory installed. If not installed, the minimum
temperature will be 23ºF (-5ºC) DB.
Indoor Unit: PEAD-A36AA4
Outdoor Unit: PUY-A36NHA4
SUBMITTAL DATA: PEAD-A36AA4 & PUY-A36NHA4. . . . . . . . . . . . .36,000 BTU/H HORIZONTAL-DUCTED AIR CONDITIONING SYSTEM
GENERAL FEATURES
• Horizontal-ducted indoor unit features medium static pressure
capability
• Thin body: 9-7/8" high
• Built-in drain mechanism for condensate removal; lifts to 27-9/16"
• Air lter is included with indoor unit
• Quiet operation—both indoor and outdoor units
• Automatic fan speed control
• Auto restart following a power outage
• Self-check function—integrated diagnostics
• Knockout for ventilation air
• Limited warranty: ve years on parts and defects and seven years
on compressors
Indoor Unit
MCA ............................................ 3.30 A
Fan Type x Quantity ......................... Sirocco fan x 2
Fan Motor Type ............. Direct-driven DC Brushless Motor
Fan Motor ....................................2.64 F.L.A.
Fan Motor Output ..................................244 W
Airow (Lo - Mid - Hi) ............. 847 - 1,024 - 1,201 Dry CFM
777 - 953 - 1,130 Wet CFM
Air Filter .........................Polypropylene Honeycomb
External Static Pressure...... 0.14 - 0.20 - 0.28 - 0.40 - 0.60"WG
Sound Pressure Level (Lo - Mid - Hi) ..........33 - 38 - 42 dB(A)
SHF ............................................. 0.75
Moisture Removal................................ 7.9 pt./h
DIMENSIONS UNIT INCHES / MM
W 55-1/8 / 1,400
D 28-7/8 / 732
H 9-7/8 / 250
Weight ....................................91 lbs. / 41 kg
External Finish .......................Galvanized-steel Sheet
Field Drainpipe Size O.D...................... 1-1/4" / 32 mm
Outdoor Unit
Compressor ...................DC Inverter-driven Twin Rotary
MCA ..............................................25 A
MOCP.............................................40 A
Fan Motor .....................................0.75 F.L.A.
Sound Pressure Level (Cooling).....................48 dB(A)
DIMENSIONS INCHES / MM
W 37-3/8 / 950
D 13 + 1-3/16 / 330 + 30
H 37-1/8 / 943
Weight ...................................163 lbs. / 74 kg
External Finish ......................Munsell No. 3Y 7.8 / 1.1
Refrigerant Type ...................................R410A
Refrigerant Pipe Size O.D.
Gas Side ................................5/8" / 15.88 mm
Liquid Side................................3/8" / 9.52 mm
Max. Refrigerant Pipe Length..................... 165' / 50 m
Max. Refrigerant Pipe Height Difference ............ 100' / 30 m
Connection Method ................................Flared
OPTIONAL ACCESSORIES
Indoor Unit
□ Filter Box with MERV 13 Filters (FBM2-4)
Outdoor Unit
□ Drain Pan (PAC-SG64DP)
□ Drain Socket (PAC-SG61DS)
□ Three-pole Disconnect Switch (TAZ-MS303)
□ Wind Bafe (WB-PA2)
□ Air Outlet Guide (PAC-SG59SG)
□ Mounting Base (DSD-400N)
□ Mounting Pad (ULTRILITE2)
□ Wall-mounting Brackets (CWMB1)
Controller Options
□ Wall-mounted Wired Remote Controller (PAR-21MAA)
□ M-NET Adapter (PAC-SF81MA)
□ CN51 Connector for Multiple Remote Controller Adapters/Duct Fan
Controller (PAC-725AD)
□ CN32 Connector for Remote On/Off (PAC-715AD)
□ Remote Temperature Sensor (PAC-SE41TS)
□ Remote Operation Adapter - Display and On/Off (PAC-SF40RM)
□ Handheld Wireless Remote Controller (PAR-FL32MA; req.
PAR-SA9CA)
□ Wireless Signal Receiver Module (PAR-SA9CA)
□ Lockdown Bracket for Handheld Controller (RCMKP1CB)
□ Control/Service Tool (PAC-SK52ST)