Model: PUMY-P60NKMU (-BS)
Model Name
Unit Type PUMY-P60NKMU (-BS)
Nominal Cooling Capacity Btu/h 60,000
Nominal Heating Capacity Btu/h 66,000
Operating Temperature Range
Cooling (Outdoor) *1
23° F ~ 115° F (-5 ° ~ +46° C) DB*
Heating (Outdoor)
-4° F ~ +60° F (-20 ° ~ +15° C) WB
External Dimensions (H x W x D) In. / mm 52-11/16 x 41-5/16 x 13 (+1-3/16) / 1,338 x 1050 x 330 (+30)
Net Weight Lbs. / kg 313 / 142
Electrical Power Requirements Voltage, Phase, Hertz
208 / 230V, 1-phase, 60Hz
Cooling Power Input kW 4.80
Heating Power Input kW 6.15
Cooling Current A 21.5
Heating Current A 27.6
Minimum Circuit Ampacity (MCA) A 35
Recommended Fuse/Breaker Size A 40
Maximum Fuse Size A 42
Piping Diameter (Brazed) (In. / mm)
Liquid (High Pressure) 3/8 / 9.52
Gas (Low Pressure) 3/4 / 19.05
Indoor Unit
Total Capacity 50 to 130% of Outdoor Unit Capacity
Model / Quantity P06 to P72 / 1 to 12
Sound Pressure Levels dB(A) 58/59
Fan
Type x Quantity Propeller Fan x 2
CFM 4,940
Compressor Operating Range 22% to 100%
Compressor Type x Quantity INVERTER-driven Scroll Hermetic x 1
Compressor Motor Output kW 3.0
Refrigerant R410A
Lubricant FV50S
High-pressure Protection Device High Pressure Switch
Compressor / Fan Protection Device Compressor Thermo / Overcurrent Detection
Inverter Protection Device Overheat / Voltage Protection
AHRI Ratings
(Ducted / Non-Ducted)
EER 11.3 / 12.5
SEER 16.5 / 16.7
COP 3.70 / 3.14
Blue Fin Anti-corrosion Protection: Cellulose- and polyurethane-resin coating treatment applied to condenser coil that protects it from air contaminants;
≥1μm thick; Salt Spray Test Method - no unusual rust development to 960 hours.
SEACOAST PROTECTION
• External Panel Base, External Front Panel, Pillar: Alloyed galvanized-steel sheets with thermoset polyester-resin coating on internal and external surfaces
• Compressor Cover: Galvanized-aluminum sheets with thermoset polyester-resin coating on internal and external surfaces
• Electrical Parts Box: Galvanized-aluminum sheets with thermoset polyester-resin coating on external surface
• Fan Motor Support: Galvanized-steel sheets with thermoset polyester-resin coating on internal and external surfaces
• Printed Circuit Board: Epoxy resin with polyurethane-coating on external surface
OUTDOOR VRF SYSTEM FEATURES
•
zoning technology
• Inverter-driven (variable speed) compressor
• Total refrigerant piping length of 492' (150 m)
• Uses CITY MULTI indoor units and Controls Network
UNIT OPTION
□ Standard Model……………………….....PUMY-P60NKMU
□ Sea Coast (BS) Model…………......PUMY-P60NKMU-BS
OPTIONAL PARTS
□ Branch Joint (T-Branch)………………………………...CMY-Y62-G-E
□ Header - Four-Branch…………………………………......CMY-Y64-G-E
□ Header - Eight-Branch…………………………………..CMY-Y68-G-E
□ Base Heater………………………………………........ PAC-SJ19BH-E
NOTES:
*1 If PKFY-P06/08 indoor units are connected, then range is 50° F ~ 115° F (10° C ~ 46° C).
PUMY-P60NKMU (-BS)