1-17
Model SRK501CENF-L (Indoor unit)
SRC501CENF-L (Outdoor unit)
(2) The operation data are applied to the 220 V or 240 V districts respectively.
(3) Limitation of Voltage application
Minimum: 198 V Maximum: 264 V
(4) The refrigerant quantity to be charged includes the refrigerant in 7.5 m connecting piping.
(Purging is not required even in the short piping.)
If the piping length is longer, (when it is less than 10 m, add 10 g refrigerant per meter and when it is 10 to 15 m, add 30 g refrigerant per meter.)
(5) Expressed in sound pressure level.
Notes (1) The data are measured at the following conditions.
Item
Model
SRK501CENF-L SRC501CENF-L
Cooling capacity
(1)
W 4500/4500
Power source 1 Phase, 220/240V, 50 Hz
Cooling input kW 1.78/1.88
Running current (Cooling) A 8.4/8.2
Inrush current A 39/42
COP (In cooling) 2.53/2.39
Noise level
(5)
dB (A) 44/44 50/51
Exterior dimensions mm
275 × 790 × 189 615 × 850 × 290 + 30
Height × Width × Depth
Color Ivory white Polar white
Net weight kg 9 52
Refrigerant equipment
– RM5523GNE4 (Rotary type) × 1
Compressor types & Q’ty
Motor kW – 1.7
Starting method – Line starting
Heat exchanger Louver fins & tubing
Refrigerant control Capillary tubes
Refrigerant
(4)
kg R22 1.28
Refrigerant oil R 0.7 (BARREL FREEZE 32SAM)
Air handling equipment
Tangential fan × 1 Propeller fan × 1
Fan type & Q’ty
Motor W 23 40
Air flow (at High) CMM 11/11 34/34
Air filter, Q’ty Polypropylene net (washable) × 2 –
Shock & vibration absorber – Cushion rubber (for compressor)
Electric heater ––
Operation control
Wireless-Remote controller –
Operation switch
Room temperature control MC. Thermostat –
Pilot lamp RUN (Green), TIMER (Yellow),
–
ECONO (Orange), HI POWER (Green)
Safety equipment – Dome mounted protector (for compressor)
Internal thermostat (for fan motor)
O.D mm (in) Liquid line: φ6.35 (1/4") Gas line: φ12.7 (1/2")
Connecting method Flare connecting
Attached length of piping Liquid line: 0.4m
–
Gas line : 0.35m
Insulation Necessary (Both sides)
Drain hose Connectable
Power source cord 2.5 m (3 cores with Earth)
Size × Core number 1.5 mm
2
× 3 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit
Optional parts –
Connection
wiring
Operation
data
(1)
Refrigerant
piping
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27°C19°C35°C24°C JIS C9612, ISO-T1