Quick start guide
IS0082A03MM_07-06-2016
ENGLISH
Note for reading this Guide • In this
Quick Start Guide, the numbering of the
figures is separate and does not cor-
respond to the numbering cited in the
complete manual. • This guide does not
substitute the complete manual.
Era Mat T
tubular motor for
awnings
Warning – The rst limit switch to be memorised must be the one with retainer of the awning against the structure (e.g. the box in limit switch “0”).
2 - Memorising the FIRST transmitter - see paragraph 5.5
1 - Electrical connections - see Chapter 4
3 - Adjust limit switches “0” and “1” in SEMIAUTOMATIC mode - ref. paragraph 5.7
4 - Total deletion of memory - ref. paragraph 5.16
2
sec.
ON
OFF
THE
5
sec.
2
3
5
sec.
2
“1”
5
sec.
03
05
THE
07
04
5
sec.
“0”
2 4
06
“1”
5
sec.
3
5
sec.
04
5
sec.
5
sec.
all
data
05
THE
END
5
sec.
5
sec.
2 3
3
3
5
Turn OFF Wait Turn ON Movements (no. 2) Press until ... Movements (no. 3) Release
END
END
END
Press until... Limit switch “0” (retainer) Release Press until ... Limit switch “1” (desired)
Press until... Movements (2) Release Press until ... Movements (4) Release
Press until ... Movements (2) Release Fine adjustments Press until ... Movements (no. 3) Release
Press until ... Movements (3) Release Press together until ... Movements (5) Release together
Press until ... Movements (2) Release Press until ... Movements (3) Release Press until ... Movements (3) Release
1
2
3
L
N
Com.
4
5
6
Cable Colour Connection
1 White-orange Clockwise rotation pushbutton
2 White Counter-clockwise rotation pushbutton / TTBus
3 White-black Common (for bus wires)
4 Brown Supply phase
5 Blue Neutral
6 Yellow-green Earth (cable not present on series “E Mat ST” motors)