Q2A 3
Common specifications
Q2A-A
Input
voltage
Duty
rating
4089 4103 4140 4168 4208 4250 4296 4371 4389 4453 4568 4675
Max. applicable motor output
(kW)
< 460 V
*1
HD 37 45 55 75 90 110 132 160 200 220 250 315
ND 45 55 75 90 110 132 160 200 220 250 315 355
≥ 460 V
*2
HD 37 45 55 75 90 110 150 185 220 260 300 335
ND 45 55 75 90 110 150 185 220 260 300 335 370
Output characteristics
Inverter capacity (kVA)
< 460 V
*3
HD 49 60 74 99 118 142 171 200 244 272 298 398
ND 59 68 92 111 137 165 195 244 256 298 374 444
≥ 460 V
*4
HD 52 61 76 99 124 143 191 241 288 330 380 410
ND 61 76 99 124 143 191 241 288 330 380 410 482
Rated output current (A)
< 460 V
HD 75 91 112 150 180 216 260 304 371 414 453 605
ND 89.2 103 140 168 208 250 296 371 389 453 568 675
≥ 460 V
HD 65 77 96 124 156 180 240 302 361 414 477 515
ND 77 96 124 156 180 240 302 361 414 477 515 605
Overload tolerance
*5
• HD: 150% of the rated output current for 60 seconds
• ND: 110% of the rated output current for 60 seconds
Carrier frequency
*6
(without derating the drive capacity)
• HD: 8 kHz
• ND: 2 kHz
• HD: 5 kHz
• ND: 2 kHz
• HD: 2 kHz
• ND: 2 kHz
Max. output voltage • Proportional to input voltage: 380-480 V
Max. output frequency
• AOLV, EZOLV: 120 Hz
• CL-V/f, CLV, AOLV/PM, CLV/PM: 400 Hz
• V/f, OLV, OLV/PM: 590 Hz
Power supply
Rated voltage and frequency
• 3-phase AC power supply 380-480 V at 50/60 Hz
• DC power supply 513-679 VDC
Allowable voltage fluctuation -15% to +10%
Allowable frequency fluctuation ±5%
Input Power (kVA)
< 460 V
HD 57 69 84 113 136 165 198 239 297 327 370 465
ND 69 84 113 136 165 198 239 297 327 370 465 523
≥ 460 V
HD 49 59 72 98 117 142 193 240 288 335 382 429
ND 73 88 120 143 174 236 295 352 410 468 526 584
Weight (kg) 22 25 38 39 71 122 126 198 207
*1. The maximum applicable motor output complies with 380 V motor ratings as specified in Annex G of IEC 60947-4-1. The rated output current of the drive
output amps must be equal to or more than the motor rated current.
*2. The maximum applicable motor output complies with 460 V motor ratings as specified in NEC Table 430.250. The rated output current of the drive output
amps must be equal to or more than the motor rated current.
*3. The rated output capacity is calculated with a rated output voltage of 380 V.
*4. The rated output capacity is calculated with a rated output voltage of 460 V.
*5. Derating may be necessary for applications that start and stop frequently.
*6. Derate the drive capacity to use values to 15 kHz maximum (4002 to 4103 models), 10 kHz maximum (4140 to 4389 models) or 5 kHz maximum (4453
to 4675 models).
Model number
Q2A-A
Specifications
Control functions
Control methods
V/f Control (V/f), Closed Loop V/f Control (CL-V/f), Open Loop Vector Control (OLV), Closed Loop Vector Control (CLV),
Advanced Open Loop Vector Control (AOLV), Open Loop Vector Control for PM (OLV/PM), Advanced Open Loop Vector
Control for PM (AOLV/PM), Closed Loop Vector Control for PM (CLV/PM), EZ Open Loop Vector Control (EZOLV)
Frequency control range
• AOLV, EZOLV: 0.01 to 120 Hz
• CL-V/f, CLV, AOLV/PM, CLV/PM: 0.01 to 400 Hz
• V/f, OLV, OLV/PM: 0.01 to 590 Hz
Frequency tolerance
• Digital inputs: ±0.01% of the max. output frequency (-10 to +40 ºC)
• Analog inputs: ±0.1% of the max. output frequency (25 ±10 ºC)
Frequency setting resolution
• Digital inputs: 0.01 Hz
• Analog inputs: 1/2048 of the max. output frequency (11-bit signed)
Output frequency resolution 0.001 Hz
Frequency setting signal
• Main speed freq reference: -10 to +10 VDC (20 kΩ), 0 to 10 VDC (20 kΩ), 4 to 20 mA (250 Ω), 0 to 20 mA (250 Ω)
• Main speed reference: Pulse train input (max. 32 kHz)
Starting torque
*1
• V/f, CL-V/f: 150%/3Hz
• OLV, AOLV: 200%/0.3Hz
• CLV, AOLV/PM, CLV/PM: 200%/0 rpm (rev/min)
• OLV/PM: 100%/5% speed
• EZOLV: 100%/1% speed
Speed control range
• V/f, CL-V/f: 1:40
• OLV, AOLV: 1:200
• CLV, CLV/PM: 1:1500
• OLV/PM: 1:20
• AOLV/PM: 1:100 (when high frequency injection is enabled)
• EZOLV: 1:100
Zero speed control Possible in these control methods: CLV, AOLV/PM, CLV/PM
Torque limits
Parameter settings allow different limits in four quadrants in these control methods: OLV, CLV, AOLV, AOLV/PM, CLV/
PM, EZOLV
Accel/Decel Time 0.0 to 6000.0 s (the drive can set four pairs of different acceleration and deceleration times)