Swimming pool heat pump
- 43 -
Description of the parameters
D——Defrost parameter
D01——Start defrost temperature
To start the defrost cycle; the condition must be valid for the time d03.
D02——End defrost temperature
Establishes the temperature above which the defrost cycle ends.
D03——Defrosting cycle
Represents delay between two successive defrost cycle. The first time, when coil
temperature is lower than D01, there must be valid for the time d03 to start defrost.
D04——Max.defrosting duration
Represents the maximum duration of the defrost cycle (the defrost ends when the
maximum duration has been arrived, even if the defrost hasn't finished)
34 Heating stop differential r07
0-10
℃
F
35 Minimum set point in Cooling r08
-30-r09
℃
F
36 Maximum Cooling set point r09
r08-80
℃
F
37
r
Minimum Heating set point r10
-30-r11
℃
F
38 Maximum Heating set point r11
r11-80
℃
F
39
S
On/off switch S01 CL/OP F/U
40 Water Flow switch S02 CL/OP F/U
41 System LP S03 CL/OP F/U
42 System HP S04 CL/OP F/U
43 Mode switch S05 CL/OP F/U
44
t
Suction temp. T01
-30~99
℃
F/U
45 Inlet water temp. T02
-30~99
℃
F/U
46 Outlet water temp. T03
-30~99
℃
F/U
47 Coil temp. T04
-30~99
℃
F/U
48 Ambient temp. T05
-30~99
℃
F/U
49
0
Compressor output O1 CL/OP F/U
50 Circulate pump output O2 CL/OP F/U
51 4-way valve output O3 CL/OP F/U
52 Fan output (High speed) O4 CL/OP F/U
53 Fan output (Low speed) O5 CL/OP F/U
54 Electronic expansion valve output O6 0~500 F/U