1. Location of Fitting
Recommended sensor upstream/downstream
mounting requirements
+
GF
+
SIGNET 515/3-8510-XX Rotor-X Paddlewheel Flow Sensor
+45°
-45°
0°
Process
Pipe
2. Sensor Mounting Position
Horizontal pipe runs: Mount sensor in
the upright (0°) position for best overall
performance. Mount at a maximum of
45° when air bubbles are present. Do not
mount on the bottom of the pipe when
sediments are present.
Vertical pipe runs: Sensor must be
mounted in lines with UPWARD flow only.
Blk
F-
Red
F+
Shld
black (AC signal out)
red (AC signal out)
silver (shield)
515/3-8510-XX Sensors
Instrument
Technical Notes
Use 2-conductor shielded cable for cable extensions up to 60 m (200 ft).
Cable shield must be maintained through cable splice.
Refer to your instrument manual for specific wiring details.
Iron
strap-on
saddles
Type Description
2 to 4 in., cut 1-7/16 in. hole in pipe
Over 4 in., cut 2-1/4 in. hole in pipe
Special order over 12 in.
0.5 to 4 in. versions
PVC or CPVC
Mounts via glue-on fittings
Plastic tees
PVC glue-on
saddles
(O-ring not
required)
2 to 4 in., cut 1-7/16 in. hole in pipe
6 to 8 in., cut 2-1/4 in. hole in pipe
Align wedge arrows with saddle arrows during assembly.
Pipes over 8 in., use iron saddle
0.5 to 2 in. versions
Mounts on threaded pipe ends
Carbon steel
threaded tees
Carbon steel
weld-on
weldolets
2 to 4 in., cut 1-7/16 in. hole in pipe
Over 4 in., cut 2-1/4 in. hole in pipe
Remove insert before welding
Installed by certified welder only
Special order over 12 in.
Metric plastic saddle
For pipes DN 65 to 200 mm
Requires a 30 mm diam. hole in the pipe
Wedge and saddle arrows must match
Metric wafer fitting
For pipes DN 65 to 200 mm
Follow the recommended installation guidelines
Metric union fitting
For pipes from DN 15 to 50 mm
PP or PVDF
Follow the recommended installation guidelines
Type Description
10x I.D. 5x I.D.
Inlet
Outlet
Flange
15x I.D. 5x I.D.
Reducer
20x I.D. 5x I.D.
90° Elbow
50x I.D. 5x I.D.
40x I.D. 5x I.D.
25x I.D. 5x I.D.
2 x 90° Elbow
2 x 90° Elbow
3 dimensions
Valve/Gate
3. Sensor Wiring
4.
+
GF
+
SIGNET Fittings
ENGLISH
"H"
5. H-Dimensions
The plastic sensor insert in the Weldolet fitting MUST be
removed during the welding process. When reinstalled, it is
important that the insert be threaded to the proper height ("H"
dimension).
Weldolet "H" dimension Weldolet "H" dimension
part number inches mm part number inches mm
CS4W020 2.38 60.45 CS4W240 4.16 105.66
CS4W025 2.33 59.18 CS4W360 4.10 104.14
CS4W030 2.32 58.92
CS4W040 2.30 58.42 CR4W020 2.38 60.45
CS4W050 3.09 78.48 CR4W025 2.33 59.18
CS4W060 2.96 75.18 CR4W030 2.32 58.92
CS4W080 2.73 69.34 CR4W040 2.30 58.42
CS4W100 5.48 139.19 CR4W050 3.09 78.48
CS4W120 5.25 133.35 CR4W060 2.96 75.18
CS4W140 5.10 129.54 CS4W080 2.73 69.34
CS4W160 4.85 123.19 CR4W100 5.48 139.19
CS4W180 4.60 116.84 CR4W120 5.25 133.35
CS4W200 4.38 111.25
SAFETY INSTRUCTIONS
1. Do not remove from pressurized lines.
2. Do not exceed maximum temperature/pressure specifications.
3. Do not install/service without following installation instructions (see sensor manual).
4. Wear safety goggles and faceshield during installation/service.
5. Do not alter product construction.
6. Failure to follow safety instructions could result in severe personal injury!
P51590-1
J-5/97

Questions and Answers: