By CAN:
Connect power cable first:
1) each pair of cable hold max 100A constant current. Connect enough pairs
of cable based on calculation of system current.
2) Suitable protection breaker between battery system and inverter is required.
3) connect power cable of LV-HUB
4) Make sure all dipswitch is X0XX, then turn ON batteries.
5) After all batteries running and buzzer of master battery in group1 rings 3
times. Means all groups are online.
6) Change the dip switch of master battery in group1 to X1XX. Then connect
communication cable between LV-HUB and master battery in group 1.
7) Then turn ON LV-HUB.
Detailed information please refer to manual of LV-HUB.