bracket
4.Fixing combiner box
Torque: 1.5-2.5 N.m
Tool: Screwdriver
Fastener: 4pcs, M4*15
Screw from right side of wall mounting bracket
5. Connect input power
cables
Ensure Disconnect
Switch is OFF
connect positive and negative cable from BMS to
combiner box Power Input Terminal.
Ensure NO reverse connection.
Ensure all cables connect in pair: 1+/1- from
same string of BMS.
6.Connect output power
cable
Ensure Disconnect
Switch is OFF
Torque: 4-5 N.m
Tool: Socket Wrench
Fastener: 2pcs, M6*10
+ -
+ -