*Wake up signal shall ≥0.5Sec, current between 5~15mA. After send wake up signal, the voltage shall
disappear for normal operation.
Input, passive signal. On: turn off battery. Off: normal.
Output1. On: stop charge.
Output2. On: stop discharge.
Output request signal voltage ≤25V
CAN
500 Kbps. 120Ω. For connection to LV-HUB, inverter, or upper battery.
RS485
9600 or 115200 bps.120Ω. For connection to inverter, or slave battery.
Link Port 0, 1
for communication between multiple parallel batteries.